CBMseries Acidic Condensate pH Treatment Kits –– Installation/Operation & Maintenance
Inspect frequently
Installer — Instruct the building owner
to frequently inspect the CBM neutral-
izer and all condensate connections. The
owner must notify a qualified technician
if any problems are noticed.
Recharge as required
When pH tube or tank outlet falls below
5PH. Local codes may have different
requirement, check with local authority.
Replacement parts
Contact your local wholesaler or manu-
facturer’s representative for replacement
parts.
Dealer listing at www.jjmboilerworks.com
69 Ferry Street - Units 17 - 20
Easthampton, MA 01027 | 413-527-1893
2400 Feather Sound Drive, Clearwater, FL 33762
413-427-3373
jjmboilerworks.com
Revised - August 2016
Maintenance
Replacement Instructions
1. Use protective rubber or plastic gloves and eye protection.
2. The neutralizer tube must be changed on a yearly basis minimum for heating systems and domestic hot water systems or
if pH at the outlet falls below 5.0pH.
3. Remove electrical power from the hot water heater, boiler or furnace.
4. Remove inlet and outlet piping and fittings from pH treatment tube.
5. Using a flat head screw driver carefully pry open the plastic brackets at the top where they connect together.
6. Remove tube from the plastic mounting brackets.
7. Remove either the barb or PVC fittings for reuse.
8. Clean “P” traps and drain piping.
9. Use old fittings and connect to the new neutralizing tube. Remount the tube by pressing the tube into the mounting
brackets using a little force which will snap the brackets arms in place. Reconnect piping and fittings. Be sure ther are no leaks.
10. Insure that condensate can flow without any blockage.
11. Dispose of the used tube properly and obey local disposal codes.
12. SDS sheet can be found on our website.