Instructions / Assembly

CBMseries Acidic Condensate pH Treatment Kits –– Installation/Operation & Maintenance
4
Figure 5
Never install the CBM
in a vertical position
as show in Figure 5.
Installation (continued)
Piping Options - Make sure the installation complies
with all local code requirements.
Piping for multiple boilers/furnaces/vent
Follow the guidelines on page 2, do not connect a flue pipe
with multiple boilers or furnaces.
As stated on page 2, do not connect a flue pipe condensate
line to the to the same neutralizer as used for a boiler/furnace
unless the boiler/furnace is individually vented, the vent will
not allow rain water to enter the flue pipe, and no other
appliance is connected to the same neutralizer tube.
C
F
B
A
E
Piping for Single Heating Unit with Condensate Pump
D
D
G
G
Condensate Drain
Figure 3
Key
A
Rev. 03/2015
Flue Drain
B
C
D
E
F
Boilers/Hot Water Heaters/Furnaces Condensate Drains
Common Flue Vent
PH Treatment Tube or Tank
House Drain
Boilers, Hot Water Heaters, Furnaces
Note: Contact Factory for PH Treatment Tube and Tank Sizing and Piping Sizing
Figure 6 Piping for Single Heating Unit with Condensate Pump
A Boilers / Hot Water Heaters / Furnace Condensate Drains
B Flue Drain
C Common Flue Vent
D pH Treatment Tube or Tank
E House Drain
F Boilers / Hot Water Heaters / Furnaces
G Condensate Drain
Note: Contact Factory for pH Treatment Tube and Tank Sizing and Pipe Sizing.
F
Y-tting By-pass with Wall Mounted Heating Unit
Figure 7
E
B
A
C
D
Do Not Mount
The PH Treatment Tube
in Vertical Position
Key
A
Rev. 03/2015
By-pass Drain
B
C
D
E
F
Boiler/Hot Water Heater/Furnace Condensate Drain
By-pass Piping
PH Treatment Tube
House Drain
Boiler, Hot Water Heater, Furnace
Note: Contact Factory for PH Treatment Tube and Tank Sizing and Piping Sizing
OUTDOOR INSTALLATIONS — provide and install electric heat tape on the condensate drain lines and around the
CBM tube to prevent possibility of neutralizer tube damage or line blockage due to freezing. Failure to comply with
the following guidelines could result in severe personal injury, death or substantial property damage.
Ratings & Dimensions (in inches)
A
C
10/2014
F F F F
B
Flue Drain
A
D
E
B
Piping for Multiple Boilers/Individual pH Treatment Kits
Common Piping
C
D
E
F
Boilers/Hot Water Heater Condensate Common Drain
Common Flue Vent
Neutralizer Tube or Tank
House Drain
Boilers, Hot Water Heaters, Furnaces
Note: Contact Factory for Neutralizer Sizing and Piping Sizing
D
D
D
D
Figure 7 Piping for Single Heating Unit with Common pH Treatment Tube or Tank
A Boilers / Hot Water Heaters / Furnace Condensate Drains
B Flue Drain
C Common Flue Vent
D pH Treatment Tube or Tank
E House Drain
F Boilers / Hot Water Heaters / Furnaces
Note: Contact Factory for pH Treatment Tube and Tank Sizing
and Pipe Sizing.