335w Silver Poly Manual
- 4 -
Do not remove any part installed by Jinko Solar or disassemble the module.
All instructions should be read and understood before attempting to install, wire, operate
and maintain the module.
Don‟t lift up PV modules using the attached cables or the junction box.
All PV systems must be grounded to earth. If there is no special regulation, please follow
the National Electrical Code or other national code.
Common hardware items such as nuts, bolts, star washers, lock washers and the like
have not been evaluated for electrical conductivity or for use as grounding devices and
should be used only for maintaining mechanical connections and holding electrical
grounding devices in the proper position for electrical conductivity. Such devices, where
supplied with the module and evaluated through the requirements in UL 1703, may be
used for grounding connections in accordance with the instructions provided with the
module.
Under normal conditions, a photovoltaic module is likely to experience conditions that
produce more current and/or voltage than reported at standard test conditions. The
requirements of the National Electrical Code (NEC) in Article 690 shall be followed to
address these increased outputs. In installations, not under the requirements of the NEC,
the value of Isc and Voc marked on the module should be multiplied by a factor of 1.25
when determining component voltage ratings, conductor ampacities, overcurrent device
ratings, and size of controls connected to the PV output.
Once the PV module has been shipped to the installation site, all of the parts should be
unpacked properly with care.
Do not stand or step on the PV module like below pictures show. This is prohibited and
there is a risk of damage to the module and cause injury for you.
Only PV modules with the same cell size should be connected in series.
During transporting modules, please attempt to minimize shock or vibration to the module,
as this may damage the module or lead to cell micro cracks.