P-00
STOP
P-01
T-BL
P-02
T-VA
P-03
SOFT
Thermostop
0= not active
1=active
default:0
Temperature boiler
Min 60C 140F
Max 95C 200F
Default 85C 185F
Temperature Tank
Set to 70C 160F
Default 60C 140F
Soft start
0= not active
1= active
default: 1 ,set to 0
AVAILABLE PARAMETERS
MAX HEATING TANK
Min 1 min
Max 60 min
DEFAULT 45 min
DON’T MODIFY
TEMPERATURE UNITS
FAR = FAHRENHEIT
CEL = CELSIUS
DEFAULT CEL=CELSIUS
OFFSET TEMPERATURE TANK
Min - 20°C
Max +20°C
DEFAULT 0°C
DON’T MODIFY
MAX HEATING BOILER
Min 5 min
Max 60 min
DEFAULT 30 min
DON’T MODIFY
REAL TEMPERATURE
0 = FILTERED
1 = REAL
DEFAULT 0 = FILTERED
DON’T MODIFY
MAX LOADING TANK
Min 1 min
Max 20 min
DEFAULT 10 min
DON’T MODIFY
MAX DRAIN TANK
Min 1 min
Max 20 min
DEFAULT 2 min
DON’T MODIFY
TEMPERATURE BOILER
Min 60°C
Max 95°C
DEFAULT 85°C
TEMPERATURE TANK
Min 40°C
Max 65°C
DEFAULT 60°C
TYPE MACHINE
Min 1
Max 2
DEFAULT SEE CHART
SOFT START
0 = not active
1 = active
DEFAULT 1=ACTIVE
OFFSET TEMPERATURE BOILER
Min - 20°C
Max +20°C
DEFAULT 0°C
THERMOSTOP
0 = not active
1 = active
DEFAULT 0=NOT ACTIVE
MODEL MACHINE
Min 1
Max 27
DEFAULT SEE CHART
P04
(DISPLAY)
P05
(DISPLAY)
MODEL
CYCLE
DRAIN PUMP
2 8
4 31 70 + 120 + 180 + 240
sec
757E
120 + 180 + 240 sec
YES
727E / 737E