Jenn-Air's ventilation system is designed to capture both cooking fumes and smoke from any
place on the grill surface, Ifthe system does not, these are some ducting installation situations
to check:
• 6" diameter round or 3T/4" xl0" rectangular ductingshould be used. Note: 5" diameter
round ducting may be used for venting straight out of the back of the cooktop and directly
through the wall for 10' or less.
• No more than three 90° elbows should be used. Distance between elbows should be at
least 18".
• Recommended Jenn-Air wall cap should be used. Make sure damper moves freely when
ventilation system is operating.
• There should be a minimum clearance of 6" for cooktop installed near a side wall.
Ifthere is notan obvious improper installation,there may be a concealed problem such as a
pinched joint, obstruction inthe pipe, etc. installationis the responsibility of the installerand
questions should be addressed first by the installer. The installershould very carefully check
the ducting installationinstructions.