User's Manual

Configuration and connection for the different protocols
Switch SW1 allows to select the short W26 (SW1= OFF) or the long W37 (SW1= ON) format.
In case the short W26 is selected, the content of the frame may be NO FC (SW2= OFF), or include a so called Facility
Code (SW2= ON).
In this case, the value of the Facility Code in Binary is set by 8 switches, each one defining either a 0= OFF or 1= ON.
Protocol Power
Remote
Control
Signal
Output SW1 SW2
Facility
Code 1 to
8 Bits FRAME FORMAT
W26 NO
Facility
Code
+ -
Button
1/2/3/4
CH1/2/3/4
D0-D1
OFF OFF don't care
EP(1)-Zeros(4)-Remote Control
Number(20)-OP(1)
W37 + -
Button
1/2/3/4
CH1/2/3/4
D0-D1
ON
don't
care
don't care
EP(1)-Counter(8)-Zeros(2)-Sub(3)-
DCS(3)-Remote Control Number(19)-
OP(1)
W26 with
Facility
Code
+ -
Button
1/2/3/4
CH1/2/3/4
D0-D1
OFF ON
mode
Facility
Code *
EP(1)-FacilityCode(8)-Remote Control
Number(16)-OP(1)
* Facility Code: SW1-8, 0=OFF/1=ON
DEC BIN DEC BIN DEC BIN DEC BIN
0 00000000 16 00010000 32 00100000 48 00110000
1 00000001 17 00010001 33 00100001 49 00110001
2 00000010 18 00010010 34 00100010 50 00110010
3 00000011 19 00010011 35 00100011 51 00110011
4 00000100 20 00010100 36 00100100 52 00110100
5 00000101 21 00010101 37 00100101 53 00110101
6 00000110 22 00010110 38 00100110 54 00110110
7 00000111 23 00010111 39 00100111 55 00110111
8 00001000 24 00011000 40 00101000 56 00111000
9 00001001 25 00011001 41 00101001 57 00111001
10 00001010 26 00011010 42 00101010 58 00111010
11 00001011 27 00011011 43 00101011 59 00111011
12 00001100 28 00011100 44 00101100 60 00111100
13 00001101 29 00011101 45 00101101 61 00111101
14 00001110 30 00011110 46 00101110 62 00111110
15 00001111 31 00011111 47 00101111 63 00111111
jcmtechnologies
6