Power Analyzer UMG 96-PQ-L (from firmware 1.0 - hardware index 1) Doc. no. 2.061.073.1.a 01/2021 Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 Email: info@janitza.de www.janitza.de Image may differ from the original! www.janitza.
UMG 96-PQ-L UMG 96-PQ-L (from firmware 1.0 / hardware index 1) Measurement device for recording energy quantities Doc. no.: 2.061.073.1.a Date: 01/2021 The German version is the original edition of the documentation 2 www.janitza.
www.janitza.de UMG 96-PQ-L Subject to technical changes. The contents of our documentation have been compiled with great care and reflect the current state of the information available to us. Nonetheless, we wish to point out that updates of this document are not always possible at the same time as technical refinements are implemented in our products. Please see our website under www.janitza.de for the current version. Please see our website under www.janitza.de for the current version.
UMG 96-PQ-L www.janitza.de TABLE OF CONTENTS 1. Information on the device and the user manual 8 1. 1 Disclaimer 8 1. 2 Copyright notice 8 1. 3 Technical changes 8 1. 4 About this user manual 8 1. 5 Defective device/disposal 9 2. Safety 10 2. 1 Display of warning notices and safety information 10 2. 2 Hazard levels 10 2. 3 Product safety 11 2. 4 Dangers when handling the device 11 2. 5 Electrically qualified personnel 12 2.
www.janitza.de UMG 96-PQ-L 6. Grid systems 26 7. Installation 27 7. 1 Nominal voltages 27 7. 1. 1 27 Three-phase four-conductor network with grounded neutral conductor 7. 2 Disconnect switch 28 7. 3 Supply voltage 28 7. 3. 1 28 7. 4 7. 5 Three-phase three-conductor system Voltage measurement 30 7. 4. 1 Overvoltage 30 7. 4. 2 Frequency 30 7. 4. 3 Connection variants for voltage measurement 31 Current measurement 32 7. 5. 1 Current direction 33 7. 5.
UMG 96-PQ-L www.janitza.de 12. Configuration 46 12. 1 The Configuration window 12. 2 Language 46 12. 3 Communication 46 12. 4 Measurement 47 12. 5 12. 6 12. 7 46 12. 4. 1 Nominal frequency 47 12. 4. 2 Nominal current 49 12. 4. 3 Current and voltage transformers 50 Display 51 12. 5. 1 Brightness 51 12. 5. 2 Standby after 51 12. 5. 3 Brightness (standby) 51 12. 5. 4 Colors 52 System 52 12. 6. 1 Firmware/Serial number 53 12. 6. 2 Date/time 53 12. 6.
www.janitza.de UMG 96-PQ-L 13. 15 Configuration of the analog output 76 13. 16 Drag indicator function 77 13. 16. 1 Internal synchronization 77 13. 16. 2 External synchronization 78 13. 16. 3 Synchronization priority 80 13. 16. 4 Drag indicator - Measurement device displays 81 13. 16. 5 Delete drag indicator 82 13. 17 Recordings 83 13. 18 Tariff switching 84 13. 19 Alarms for “Low battery voltage” and “Set time” 85 14. Overview of measuring displays 86 15.
UMG 96-PQ-L 1. 1.1 Information on the device and the user manual Disclaimer Compliance with the usage information for the devices is a prerequisite for safe operation and attaining the stated performance characteristics and product features. Janitza electronics GmbH assumes no liability for bodily injury, material damage or financial losses which result from disregard of the usage information. Make sure that your usage information is readily available and legible. 1.
www.janitza.de 1.5 UMG 96-PQ-L Defective device/disposal Before sending defective devices, modules or components back to the manufacturer for testing: · Contact the manufacturer's Support department. · Send devices, modules or components complete with all accessories. · When doing so, please bear the terms for transportation in mind.
UMG 96-PQ-L 2. Safety The chapter on Safety contains information which must be observed to ensure your personal safety and avoid material damage. 2.1 www.janitza.de Display of warning notices and safety information The warning notices shown below · are found throughout all of the documentation, · can be found on the devices themselves. · indicate potential risks and hazards, · underscore aspects of the information provided that clarifies or simplifies procedures.
www.janitza.de 2.3 Product safety The device reflects current engineering practice and accepted safety standards, but hazards can arise nonetheless. Observe the safety regulations and warning notices. If notices are disregarded, this can lead to personal injury and/or damage to the product.
UMG 96-PQ-L 2.5 www.janitza.
www.janitza.de UMG 96-PQ-L CAUTION Risk of injury or damage to the meter/your system due to short circuit! Inadequate insulation of the operating equipment at the residual current measuring input with respect to the supply circuits can cause voltages at the measuring input which represent a hazard when touched or damage to your device or system.
UMG 96-PQ-L www.janitza.de 3. Product description 3.1 Device description The device is a multifunctional network analyzer and is suitable for: · Measurements and calculations of electrical quantities such as voltage, current, power, energy, harmonics current in building installations, on distribution boards, circuit breakers and busbar trunking systems. · Measurements of voltages and currents from the same network.
www.janitza.de 3.3 UMG 96-PQ-L Intended use The device is: · Only for use in the industrial sector. · Intended for installation in switchboard cabinets and small installation distributors. · Not intended for installation in vehicles! Use of the device in non-stationary equipment constitutes an exceptional environmental condition and is only permissible by special agreement. · Not intended for installation in environments with harmful oils, acids, gases, vapors, dusts, radiation, etc.
UMG 96-PQ-L 3.4 Performance characteristics General · Front panel installation device with dimensions of 96 x 96 mm (3.78 x 3.78 in).
www.janitza.de 3.7 Scope of delivery Quantity Part. no. Designation 1 52.32.xxx 1) UMG 96-PQ-L 1 33.03.389 Installation instructions 1 33.03.342 Supplement “Safety Information” 1 33.03.361 “GridVis Software” Quick Guide 1 10.01.896 1 10.01.849 1 10.01.871 1 10.01.909 1 10.01.
UMG 96-PQ-L 3.9 Measuring method The device measures · Continuously and calculates all effective values using in a 200 ms interval. · The true RMS value (TRMS) of the voltages and currents applied to the measuring inputs. 3.10 Transformer Please note! It is not permitted to use the outputs of Janitza measurement devices and components for switching protective devices or protective relays! Use only “Current transformers for measuring purposes” for Janitza measurement devices and Janitza components! 3.
www.janitza.
UMG 96-PQ-L 4. www.janitza.de Structure of the device Front panel - Display and controls Image may differ from the original! 4.1 8 7 Fig. Front view UMG 96-PQ-L 1 Item 3 4 5 6 7 Function/Designation Button 1: · Display Menu · Exit Menu · Cancel action (ESC) Button 2: · Go to the start screen. (Default setting: “Overview” display) · Select position (to the left “”). · Configuration of a measuring display as the start screen (press until message appears).
www.janitza.de 4.2 UMG 96-PQ-L Rear of the device - Connections 2 3 4 5 6 7 1 8 Fig.
UMG 96-PQ-L 4.3 www.janitza.de UMG 96-PA Rating plate UMG 96-PQ-L 5 6 7 UM 4 3 1 2 UMG 96xxx 1234567 Aux: 90..277V, 50/60Hz . 90..250V . 4,5VA 300V CAT III Made in Germany • www.janitza.com Item Designation 8 10 11 Description 1 Operational data · · · · · 2 Part number Manufacturer’s part number 3 Symbol for “Danger sign” General hazard symbol.
www.janitza.
UMG 96-PQ-L 5. 5.1 www.janitza.de Mounting Installation location DANGER Danger of electric shock! Electric shocks lead to serious injuries, including death. · Disconnect your system from the power supply before mounting and connecting the device! · Secure it against being switched on! · Check to be sure it is de-energized! · Ground and short circuit! · Cover or block off adjacent live parts! · The installation must only be carried out by qualified personnel with electrical training! 5.
www.janitza.de 5.3 UMG 96-PQ-L Securing Secure the device inside the switchboard (mounting plate) with the fastening clips on the side. To do so, proceed as follows: · Before inserting the device, remove the fastening clips (e.g. with a screwdriver) by levering them horizontally. Fig. Side view of UMG 96-PQ-L with fastening clip. · Guide the device through the switchboard (mounting plate) from the front. · Attach the clips to the side of the device by pushing them in and snapping them into place.
UMG 96-PQ-L 6. www.janitza.
www.janitza.
UMG 96-PQ-L 7.1.2 www.janitza.de Three-phase three-conductor system Networks and nominal voltages suitable for your device: UL-L 100 V 120 V 200 V 240 V 347 V 380 V 400 V 415 V 440 V 480 V 600 V INFORMATION Maximum nominal voltage of the network according to IEC and UL Fig. Nominal network voltages suitable for measuring inputs according to EN 60664-1:2003 (valid in three-phase three-conductor systems - see section “Grid systems”). 7.
www.janitza.de UMG 96-PQ-L L N PE/FE 1) 2) Functional earth Overcurrent protective device for the line protection of the supply voltage 1) Fuse (UL/IEC listed) 2) Isolation device (disconnect switch or circuit breaker) Recommendation for the overcurrent protective device of the supply voltage line protection (dependent on the device variants): · Option 230 V --> 6 - 16 A (Char. B) · Option 24 V * --> 1 - 6 A (Char.
UMG 96-PQ-L 7.4 www.janitza.de Voltage measurement There are 3 voltage measurement inputs (V1 to V3) on the rear of the device. 7.4.1 Overvoltage The voltage measurement inputs are suitable for measurement in networks where overvoltages of category 600 V CAT III (rated surge voltage 6 kV) can occur. 7.4.2 Frequency The device: · Requires the mains frequency for the measurement and calculation of measured values.
www.janitza.de UMG 96-PQ-L Fig.: Voltage measurement in a three-phase 3-conductor system with voltage transformer. INFORMATION · The device only determines measured values if a voltage L1-N of greater than 20 Veff (4-conductor measurement) or a voltage L1-L2 of greater than 34 Veff (3-conductor measurement) is applied to voltage measurement input V1. · Use a line protection (1-10 A) with IEC/UL approval as an overcurrent protective device for voltage measurement. 7.4.
UMG 96-PQ-L 7.5 www.janitza.de Current measurement The device: · Is designed for the connection of current transformers with secondary currents of ../1 A and ../5 A. · Is only approved for current measurement via current transformers. · Does not measure DC currents. The factory-set current transformer ratio is 5/5 A and must be adapted to the current transformers used as needed.
www.janitza.de 7.5.1 UMG 96-PQ-L Current direction 7.5.3 You can correct the current direction for each phase individually via the serial interfaces provided. This means that in the case of incorrect connection, no subsequent reconnection of the current transformers is necessary. 7.5.2 Ammeter If you want to measure the current not only with the UMG, but also with an ammeter, connect the ammeter to the UMG in series.
UMG 96-PQ-L 7.5.4 www.janitza.de Connection variants for current measurement Fig.: Current measurement via current transformer in a three-phase 4-conductor system Load Fig.: Current measurement via current transformer in a three-phase 3-conductor system Load Fig.: Current measurement via 2 current transformers (Aron circuit) in a three-phase 3-conducLoad tor system Fig.: Current measurement via 2 current transformers (Aron circuit) in a three-phase 4-conductor system Load Load Fig.
www.janitza.
UMG 96-PQ-L 8. 8.1 www.janitza.de Connection and PC connections Connection variants When connecting the device to a PC, there are several possibilities: 1. Connection via an interface converter: PC with GridVis® UMG 96-PQ-L RS-232 RS-232 RS-485 RS-485 PC with GridVis® UMG 96-PQ-L USB USB RS-485 RS-485 1. Use of the UMG 96-PQ-L (server device) via a UMG with gateway functionality (e.g.
www.janitza.de 8.2 UMG 96-PQ-L RS-485 interface 8.3 The device communicates with the Modbus RTU protocol via an RS-485 interface (3-pole plug contact). Recommended cable type: · Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cable) e.g. connection to the UMG 604 as a gateway (client device) Data GND Connection capacity of the terminal: · 0.2 - 1.5 mm2 (see the chapter “Technical Data”) RS-485 bus A e.g.
UMG 96-PQ-L 8.4 www.janitza.de Termination resistors At the beginning and end of a segment, the cable is to be terminated with resistors (120 Ω, 1/4 W). INFORMATION The device does not contain an integrated termination resistor! Right Wrong Terminal strip in the switchboard cabinet. Device with RS-485 interface. (Without termination resistor) Device with RS-485 interface. (With termination resistor on the device) 38 8.5 Bus structure In a bus structure: · Connect all devices in line.
www.janitza.de UMG 96-PQ-L Fig. Representation of a bus structure * Client device T T Server device Server device Server device Repeater T T Server device T * Server device Server device Server device Power supply necessary Client device - e.g. UMG 604-PRO Bus terminator on Server device - UMG 96PA In a Modbus system the Modbus organization (modbus.
UMG 96-PQ-L 9. www.janitza.de Digital inputs and outputs The device has: · 3 digital inputs and · 3 digital outputs 24 VDC UMG 96-PQ-L Digital inputs 1-3 The device recognizes an input signal at the digital input if: · A voltage of at least 18 V and at most 28 V DC (typically at 4 mA) is present. · A current of at least 0.5 mA and at most 6 mA flows. + 17 18 2k21 LED The device has three digital inputs for the connection of, for example, one signal generator each.
www.janitza.de Digital outputs External auxiliary voltage The device has 3 digital outputs, which: · Are electrically isolated from the evaluation electronics via optocouplers. · Have a common reference. · Are not short-circuit proof. · Require an external auxiliary voltage. · Can be used as impulse outputs. · Are able to switch direct and alternating current loads. · Can be controlled via Modbus. · Output the results of comparators.
UMG 96-PQ-L www.janitza.de 10. Analog outputs The device has 1 passive analog output which can deliver a current of 0 - 20 mA. An external power supply unit (24 V DC) is required for operation. The connectable load must not exceed a resistance of 300 ohms. If the analog output is loaded with a higher resistance, the output range (20 mA) is restricted.
www.janitza.de UMG 96-PQ-L 11. Operation The device is operated via 6 function buttons which have different functions: · Selecting measuring displays. · Navigation within the menus. · Editing device settings. 1 2 11.2 Measuring display “Overview” Start screen, UMG 96-PQ-L: After restoration of network power, the UMG 96PQ-L starts with the measuring display Overview. The measuring display Overview contains the device name and an overview of important measured values.
UMG 96-PQ-L 11.4 www.janitza.de Overview of menu displays Drag indicator Current Menu Current L1 Overview (UMG 96-PQ-L start screen - default setting) Current L2 Current L3 Active power Voltage Voltage L-N (3P4W network only) Voltage L-L History Phasor diagram 1 Current Current THD-I History History L4 (3P4W network only) Active power L1 Active power L2 Active power L3 Active power L1 ..
www.janitza.de UMG 96-PQ-L Configuration Language German English Communication/Fieldbus Device address Select the menu item: · Use buttons 3 () and 4 () to select the menu item. · Confirm this with button 6 (Enter). · Use button 1 (Esc) to leave the selection. · Use button 2 (Home) to go to the start screen “Overview” (default setting).
UMG 96-PQ-L www.janitza.de 12. Configuration 12.1 The Configuration window The Configuration menu of the device contains all parameters in which you make settings. The device requires the supply voltage for configuration. To do so, proceed as described in 13.1 on page 60: · Use button 2 (Home) to go to the start screen Overview (default setting). · Open the menu with button 1 (Menu). · Use buttons 3 () and 4 () to select the menu item “Configuration” and confirm with button 6 (Enter). 12.
www.janitza.de Fig. Communication window for fieldbus parameters (RS-485 interface) · Use the Communication window to configure the parameters for the fieldbus (RS-485 interface), such as Device address, Baud rate and Data frame by selecting the respective item and confirming with button 6 (Enter). · Depending on the parameter selected, the corresponding entry is shown in “yellow”.
UMG 96-PQ-L · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item Measurement and confirm with button 6 (Enter). · The Measurement window appears with the entries: - Transformer. - Nominal current. - Nominal frequency. · Use buttons 3 () and 4 () to select the item www.janitza.
www.janitza.de 12.4.2 UMG 96-PQ-L Nominal current For a defined operation of the device, you need the nominal current in addition to the settings of the current and voltage transformer ratios. · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item Measurement and confirm with button 6 (Enter). · The Measurement window appears. · Use buttons 3 () and 4 () to select the item Nominal current and confirm with button 6 (Enter). Fig.
UMG 96-PQ-L 12.4.3 Current and voltage transformers INFORMATION Before configuring the current and voltage transformer ratios, be certain to connect the transformers in compliance with the specifications on the device rating plate and the technical data! · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item Measurement and confirm with button 6 (Enter). · The Measurement window appears.
www.janitza.de 12.5 Display Use the item Display of the measurement device to configure the following display settings: · Brightness, · Standby after, · Brightness (standby) and · Colors. · Open the Configuration window as previously described. UMG 96-PQ-L · Confirm your entries with button 6 (Enter) or end the action by pressing button 1 (Esc). · To return to the start screen, press button 1 twice (Esc) and then press button 2 (Home). 12.5.1 Brightness Display brightness of the measurement device.
UMG 96-PQ-L 12.5.4 Colors Colors for the display of current and voltage in the graphical visualizations. · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item Display and confirm with button 6 (Enter). · The Display window appears. · Use the buttons 3 () and 4 () to select the item Colors and confirm with button 6 (Enter). · The Colors window appears. www.janitza.de 12.
www.janitza.de 12.6.1 Firmware/Serial number The firmware and the serial number of the measurement device are required for support requests or registration on the homepage (www.janitza.de). 12.6.2 Date/time Setting the date and time. You can change the settings for synchronization, the date and time zones via · the GridVis® software or · the Modbus addresses (See section “14.12 Synchronization” on page 53). 12.6.
UMG 96-PQ-L 12.6.4 Reset This function is used to delete and reset measured values and device parameters. Energy You can delete all energy meters in the device simultaneously. It is not possible to select certain energy meters. · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item System and confirm with button 6 (Enter). · The System window appears. · Use buttons 3 () and 4 () to select the item Reset and confirm with button 6 (Enter).
www.janitza.de UMG 96-PQ-L Standard factory settings Restart This function resets all settings, such as configurations and recorded data, to the factory settings. · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item System and confirm with button 6 (Enter). · The System window appears. · Use buttons 3 () and 4 () to select the item Reset and confirm with button 6 (Enter). · The Reset window appears.
UMG 96-PQ-L 12.7 Modbus editor The function Modbus Editor is used to configure various functions or to read out measured values directly on the measurement device, without parametrization software or a network connection. Your measurement device does not require a network connection for this. www.janitza.de INFORMATION Further information on the analog outputs can be found in section „10. Analog outputs“ on page 42 and in section „13.15 Configuration of the analog output“ on page 76.
www.janitza.de You can access the Modbus editor as follows: · Open the Configuration window as previously described. · Use buttons 3 () and 4 () to select the item Modbus editor and confirm with button 6 (Enter). Fig. Configuration window, Modbus editor · The Communication window appears with the Modbus editor. UMG 96-PQ-L Example for the measured value Active power: · In the Configuration window, select the item Modbus editor and confirm with button 6 (Enter).
UMG 96-PQ-L 12.7.1 www.janitza.de Network system configuration via the Modbus editor Configure the network system for your measurement device in Modbus address 117 in the Modbus editor of the measurement device.
www.janitza.de UMG 96-PQ-L INFORMATION As an option to network system configuration on the measurement device (Modbus address 117), you can configure the network systems in the GridVis® software. To do so, use one of the 3 types of measurement device connections to a PC running the GridVis® software: · Via a measurement device with gateway functionality (see section „8. Connection and PC connections“ on page 36). · Via an interface converter (see section „8. Connection and PC connections“ on page 36).
UMG 96-PQ-L www.janitza.de 13. Commissioning 13.1 Applying the supply voltage 1. Connect the supply voltage with a terminal on the back of the device. 2. After connection of the supply voltage, the start screen Overview appears (default setting) on the display of your measurement device. 3. If no display appears, check whether the supply voltage is within the nominal voltage range.
www.janitza.de 13.4 UMG 96-PQ-L Frequency For the measurement and calculation of measured values, the device requires the nominal or mains frequency. The mains frequency can either be specified by the user or determined automatically by the device. · To determine the mains frequency, the voltage measurement input V1 requires a voltage greater than 20 Veff (4-wire measurement) or an L1-L2 voltage of greater than 34 Veff (3-wire measurement). · The mains frequency must be in the range from 45 Hz to 65 Hz.
UMG 96-PQ-L 13.5.1 www.janitza.de Fundamentals on the phasor diagram The phasor diagram graphically describes the phase shift or phase angle between the voltage and the current. The phasors rotate at a constant angular speed – proportional to the frequency of the voltage and current – around an origin. The phasor diagram thus shows the momentary state of the variables in an AC circuit. Representation of capacitance: · The current is ahead of the voltage.
www.janitza.de 13.6 UMG 96-PQ-L Checking of voltage and current inputs by means of phasor diagram The phasor diagram can be used to check incorrect connections at the voltage and current inputs. Example 1 Primarily ohmic load. Voltage and current have only a small deviation in the phase position. · The current measurement input is assigned to the correct voltage measurement input Example 2 Primarily ohmic load. 13.
UMG 96-PQ-L 13.9 Control of the power measurement www.janitza.de 13.10 Control of the communication Short-circuit all current transformer outputs except one and check the indicated powers. The device counts all received (RX), all sent (TX) and all faulty data packets. · The device must only display power in the phase with the current transformer input that is not short-circuited. · If this is not the case, check the connection of the measured voltage and measured current.
www.janitza.de UMG 96-PQ-L Now check the RS-485 communication parameters, such as: · All received (RX), all sent (TX) and all faulty data packets. Ideally, the number of errors in the column Error will equal “0”. · The mode that is set, the device address, baud rate and timeout. Check the parameters of the measurement device to the digital inputs and outputs and the analog output as follows: · If you are not in the start screen, you can go to this view by pressing button 2 (Home).
UMG 96-PQ-L 13.11 Delete min./max. values In the measuring displays for voltage, current and power, the device offers the function of deleting Min./Max. values using button 6 (Enter). The Min./ Max. values can be deleted for the following measured values: In the submenu Voltage: · Voltage L-N · Voltage L-L In the window Current: · Current · THD-I (Total harmonic distortion - current) www.janitza.de · The submenu for Voltage appears.
www.janitza.
UMG 96-PQ-L www.janitza.de 13.12 Harmonics current (harmonics) Harmonics current (harmonics) are caused, for example, by equipment with non-linear characteristics. These additional frequencies represent the integral multiple of a fundamental oscillation and show how the equipment affects the mains. Possible effects of harmonics are, for example: · Additional heating of operating equipment. · An additional current on the neutral conductor. · An overload and a reduced service life of electrical consumers.
www.janitza.de UMG 96-PQ-L 13.13 Communication in the bus system 13.13.1 RS-485 The device sends and receives data via the RS485 interface. For example, the device receives data from the parameter and measured value list via a MODBUS RTU protocol with CRC check. Modbus functions (server device) 03 Read Holding Registers 04 Read Input Registers 06 Preset Single Register 16 (10Hex) Preset Multiple Registers 23 (17Hex) Read/Write 4X Registers The order of the bytes is high before low byte (Motorola format).
UMG 96-PQ-L www.janitza.de 13.14 Digital inputs/outputs Your device has three digital outputs and three digital inputs. + - = 24V = DC + - K1 21 22 K2 23 S1 S2 S3 K3 24 Digital Outputs 17 18 19 20 Digital Inputs Fig. Digital outputs and inputs · You configure the digital inputs and outputs using the GridVis® software · The GridVis® software is available for download from our website (www.janitza.de). 13.14.
www.janitza.de UMG 96-PQ-L Pulse counter All digital inputs can be operated with a frequency of 25 Hz. The pulse duration (pulse width) and the pulse pause must be greater than 20 ms. The typical pulse duration for S0 pulses is 30 ms.
UMG 96-PQ-L 13.14.
www.janitza.de UMG 96-PQ-L 3. Calculate pulse valency: Pulse valency = The weekly timers are configured using the GridVis® software in the “Timer” configuration area) Max. connected load Max. number of pulses/h [Pulses/Wh] Pulse valency = 135 kW / 60000 pulses/h Pulse valency = 0.00225 pulses/kWh Pulse valency = 2.25 pulses/Wh External 230 VAC operating voltage 24 VDC + - UMG 96-PQ-L Switching and pulse outputs 21 +24V= Digital Output 1 Data logger 22 1.5k Fig.
UMG 96-PQ-L Output for comparator group Two comparator groups (comparator 1 and 2) each with 3 comparators (A - C) are available for monitoring limit values. The results of comparators A to C can be linked with “AND” or “OR”. www.janitza.de 4 5 6 3 2 1 The logic result of comparator group 1 can be assigned to digital output 2 and the logic result of comparator group 2 can be assigned to digital output 3.
www.janitza.de UMG 96-PQ-L Comparator running time Comparator running times are time counters that add up continuously for a set comparator output. This means that if the condition of the comparator is fulfilled and the lead time has expired, the counter increases by the corresponding amount of time - the minimum initialization time is not considered here! Measured value Limit value Limit violation (e.g.
UMG 96-PQ-L www.janitza.de 13.15 Configuration of the analog output The device has an analog output that can output a maximum current of 20 mA. An external 24 VDC power supply unit is required for operation. “Peripherals”. Examples: Allocation of active power L1 (output range 4 - 20 mA) 20 mA 20 mA 4 mA 1000 W End value 500 W Start value 4 mA 230 V Start value 250 V End value Fig.
www.janitza.de 13.16 Drag indicator function The “Drag indicator” function describes the 3 highest average values of value types over a defined period (time base). · The device displays the measured maximum average values in the Drag Indicator menu (see section „13.16.4 Drag indicator - Measurement device displays“ on page 81). · The average values determined can be called up via the GridVis® software and via a parameter with a time stamp.
UMG 96-PQ-L www.janitza.de 13.16.2 External synchronization An external synchronization for the calculation of the 3 highest average values is performed: · via digital input 3 (e.g. via a pulse generator) or · via a Modbus command.
www.janitza.de UMG 96-PQ-L “Periodic pulses” If the device receives periodic pulses via digital input 3 or periodic Modbus commands, there are different scenarios. Capture time Capture time Capture time Capture time Time base Time base Time base Scenario “Pulse before time base, within the capture time”: · Perform value calculation now. · The time is set to 0 (new relative zero point). · Delete summed intermediate values.
UMG 96-PQ-L 13.16.3 Synchronization priority An external synchronization takes place according to different priorities: · Priority 1: Modbus synchronization For this, set the “Enable flag” (addr.: 822) using the Modbus tool or select the “Synchronization via Modbus” option in the GridVis® software in the drag indicator configuration area. · Priority 2: Synchronization via digital input 3 For this, set the Modbus parameter “FUNC_ SYNC_RECORD” (addr.
www.janitza.de UMG 96-PQ-L 13.16.4 Drag indicator - Measurement device displays As already described in section “13.16 Drag indicator function”, the drag indicator function shows the 3 highest average values of value types over a defined period (time base). The drag indicators of the respective measured value types can be called up on the measurement device display under Menu > Drag indicator.
UMG 96-PQ-L 13.16.5 Delete drag indicator In each drag indicator display of the device - current, active and apparent power - a dialog box for deleting the drag indicator values appears when button 6 is pressed: Fig. Dialog box for deleting the drag indicator values INFORMATION The deletion of current, active power or apparent power drag indicator values of one phase also causes the deletion of the drag indicator values for the other phases of the respective category.
www.janitza.de 13.17 Recordings The standard setting of the measurement device includes 2 recording profiles that you can adapt or expand in the GridVis® software. · The smallest time base for recordings is 1 minute. · A maximum of 4 recordings with 29 measured values each is possible. If min. and max. values are defined as well, the number is reduced to 19 or 14 values respectively.
UMG 96-PQ-L 13.18 Tariff switching The recording of electrical energy values (active, reactive and apparent energy) is done via internal meters for two tariffs each. www.janitza.de INFORMATION Configure tariff switching using the GridVis® software! Switching between the tariffs (HT/LT) is supported by: · Modbus, · digital input 1 (see section “Digital inputs”) or · the weekly timer (see section “Timer switch output”) Fig.
www.janitza.de UMG 96-PQ-L 13.19 Alarms for “Low battery voltage” and “Set time” After a battery replacement, an alarm appears on the device display stating “Please set time”.
UMG 96-PQ-L www.janitza.de 14. Overview of measuring displays Menu (overview) Menu (Voltage) Network analysis (Start screen) Three-phase four-wire system Display of · Voltage L1-N, L2-N, L3-N, frequency; · Current L1, L2, L3 and sum of L1..L3; · Power L1, L2, L3 and sum of L1..L3; · Power factor and sum of L1..L3; · Sum of active and reactive energy L1-L3 Three-phase three-wire system Display of · Voltage L1-L2, L2-L3, L3-L1, frequency; · Current L1, L2, L3 and vectorial sum of L1..
www.janitza.de Menu (Current) UMG 96-PQ-L Current THD-I Display of current L1, L2, L3 and their min. / max. values Display of distortion factors for the current (THD-I) L1, L2, L3 and their min. / max. values History Display of current histories L1, L2, L3 Menu (Power) Total power Displays sum (L1..L3) of active, reactive and apparent power and their min./max.
UMG 96-PQ-L Menu (Energy) Menu (consumption overview) 88 www.janitza.de Active, reactive, apparent energy Tariff Displays sum (L1..L3) of active, reactive and apparent energy Displays the sum (L1..
www.janitza.de UMG 96-PQ-L Menu (drag indicator) Voltage L1, L2, L3 Current Drag indicator display of the currents L1, L2 and L3 with the 3 maximum values and a time stamp. Active power (Appl. and Del.) L1, L2, L3 Active power sum (Appl. and Del.) L1..L3 Drag indicator display of the active powers L1, L2 and L3 (App. and Del.) with the 3 maximum values and a time stamp. Drag indicator display of the active power sum L1..L3 (App. and Del.) with the 3 maximum values and a time stamp.
UMG 96-PQ-L Menu (Harmonics) Menu (oscilloscope) 90 www.janitza.de Voltage L1 / L2 / L3 Voltage L1 / L2 / L3 Display of the harmonics up to the 65th harmonic (voltage L1, L2, L3) Display of the harmonics up to the 65th harmonic (current L1, L2, L3) Voltage L1 / L2 / L3 Voltage L1..L3 Display oscillogram of voltage L1, L2 or L3 Display oscillogram of voltages L1, L2 and L3 Voltage L1 / L2 / L3 Current L1..
www.janitza.de UMG 96-PQ-L Menu (System Info) For information on the items in the Configuration window, see section „12. Konfiguration“ auf Seite <ÜS> Submenu System Info Com. RS-485 Peripherals Display of received (RX), transmitted (TX) and faulty data packets, RS-485 mode, device address, baud rate and timeout. Display of the states of the digital inputs and outputs, value of the analog output.
UMG 96-PQ-L www.janitza.de 15. Overview of configuration displays Menu (Configuration) For information on the items in the Configuration window, see section „12. Configuration“ on page 46 Language Setting the language to German. Setting the language to English. Communication Fieldbus settings device address, baud rate and data frame. Measurement Settings of the transformers, the nominal current and the nominal frequency. 92 Settings of current and voltage transformers (primary and secondary).
www.janitza.de UMG 96-PQ-L Display Settings for brightness, standby time after, brightness (standby) and the display colors for voltage and current (L1, L2, L3). Settings for the display colors of voltage and current (L1, L2, L3). Firmware version, serial number. Setting the time, password and resetting measured values. Resetting of energy measured values, min. and max. values. Reset to standard factory settings or restart of the measurement device.
UMG 96-PQ-L www.janitza.de 16. Service and maintenance Prior to outbound delivery, the device is subjected to various safety tests and is marked with a seal. If a device is opened, the safety tests must be repeated. A warranty is only assumed for unopened devices. 16.
www.janitza.de 16.6 UMG 96-PQ-L Clock/Battery The supply voltage supplies the internal clock of the meter. If the supply voltage fails, the battery takes over the supply of voltage to the clock. The clock provides date and time information, for example for recordings and min. and max. values.
UMG 96-PQ-L www.janitza.de 17. Procedure in the event of a malfunction Failure mode Cause Remedy No display External fuse for the supply voltage has tripped. No measured voltage connected. Replace fuse. No measured current connected. Connect measured current. No current display. Displayed current istoo great or too small. Current measurement on the wrong phase. Current transformer factor incorrectly programmed. The peak current value at the measuring input was exceeded by current harmonics.
www.janitza.de UMG 96-PQ-L 18. Technical data General Net weight (with attached plug-in connectors) Package weight (incl. accessories) Battery Data memory Backlight service life Impact resistance approx. 250 g (0.55 lbs) approx. 500 g (1.1 lbs) Type Lithium CR2032, 3 V, (UL 1642 approved) 64 MB 40000 h (backlight reduces to approx.
UMG 96-PQ-L www.janitza.de Voltage measurement Three-phase 4-conductor systems with rated voltages up to Three-phase 3-conductor systems with rated voltages up to 417 V / 720 V (+-10%) according to IEC 347 V / 600 V (+-10%) according to UL 600 V (+10%) Single-phase 2-conductor system with rated voltages up to 480 V (+-10%) Overvoltage category 600 V CAT III Rated surge voltage 6 kV Protection of the voltage measurement 1 - 10 A (with IEC/UL approval) Measuring range L-N 01) .. 600 Vrms (max.
www.janitza.de UMG 96-PQ-L Analog outputs External power supply max. 33 V Current 0 .. 20 mA Update time 1s Load max. 300 Ω Resolution 10 bit Connecting capacity of the terminals (supply voltage) Connectible conductors. Only connect one conductor per terminal point! Single core, multi-core, fine-stranded 0.2 - 4.0 mm2, AWG 28-12 Wire ferrules (non-insulated) 0.2 - 2.5 mm2, AWG 26-14 Wire ferrules (insulated) 0.2 - 2.5 mm2, AWG 26-14 Tightening torque 0.4 - 0.5 Nm (3.54 - 4.
UMG 96-PQ-L www.janitza.de 19. Performance characteristics of functions Function Symbol Accuracy class Measuring range Display range Total active power P 0.5 (IEC61557-12) 0 W .. 12.6 kW 0 W .. 999 GW * Total reactive power QA, Qv 1 (IEC61557-12) 0 var .. 16.6 kvar 0 var .. 999 Gvar * Total apparent power SA, Sv 0.55) (IEC61557-12) 0 VA .. 12.6 kVA 0 VA .. 999 GVA * Total active energy Ea 0.2 0.2S5) 0 Wh .. 999 GWh 0 Wh ..
www.janitza.
UMG 96-PQ-L 19.1 www.janitza.
www.janitza.de Address 19096 19098 19100 19102 19104 19106 19108 19110 19112 19114 19116 19118 19120 19.2 Format float float float float float float float float float float float float float UMG 96-PQ-L RD/WR RD RD RD RD RD RD RD RD RD RD RD RD RD Variable _IQH[1] _IQH[2] _IQH_SUML13 _CQH[0] _CQH[1] _CQH[2] _CQH_SUML13 _THD_ULN[0] _THD_ULN[1] _THD_ULN[2] _THD_ILN[0] _THD_ILN[1] _THD_ILN[2] Number formats Unit varh varh varh varh varh varh varh % % % % % % 19.
UMG 96-PQ-L 19.4 www.janitza.de Dimensional drawings 3.78 in 6 mm 96 mm 0.24 in 0.19 in 4,9 mm · The figures are for illustration purposes only and are not to scale. 3.43 in 87,2 mm 3.78 in 96 mm Battery 96 mm 3.78 in Fig. Front view 1) Bottom view 92+0,8 mm 92+0,8 mm Fig. Side view 104 87,2 mm 6 mm 3.43 in 0.24 in Fig. Cutout dimensions 3.62+0.03 in 3.62+0.
www.janitza.de 19.
Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Tel.: +49 6441 - 9642-0 Fax: +49 6441 - 9642-30 Email: info@janitza.de info@janitza.de | www.janitza.de Doc. no. 2.061.073.1.a | Date 01/2021 | Subject to technical changes. The latest version of the document can be found in the download area at www.janitza.de.