Data Sheet
03/2021 • Data sheet UMG 96-PQ-L – 3
UMG 96-PQ-L
TECHNICAL DATA
Transport and storage
The following information applies to devices that are transported or stored in their original packaging.
Free fall 1 m (39.37 in)
Temperature -25 °C (-13 °F) to +70 °C (158 °F)
Relative air humidity (non-condensing) 0 to 90% RH
Environmental conditions during operation
Install the device in a weather-protected and stationary location.
Protection class II according to IEC 60536 (VDE 0106, Part 1).
Rated temperature range -10 °C (14 °F) .. +55 °C (131 °F)
Relative air humidity (non-condensing) 0 to 75 % RH
Operating elevation 0 .. 2000 m (1.24 mi) above sea level
Pollution degree 2
Mounting orientation As desired
Ventilation No forced ventilation required.
Protection against foreign matter and water
- Front
- Rear
- Front with seal
IP40 according to EN60529
IP20 according to EN60529
IP54 according to EN60529
Electromagnetic environmental conditions Class E2 (MID 2014/32/EU)
Mechanical environmental conditions Class M1 (MID 2014/32/EU)
General
Net weight (with attached plug-in connectors) approx. 250 g (0.55 lb)
Package weight (incl. accessories) approx. 500 g (1.1 lb)
Battery Type Lithium CR2032, 3 V (Zulassung nach UL 1642)
Data memory 64 MB
Backlight service life 40000 h
(backlight reduces to approx. 50% over this period)
Impact resistance IK07 according to IEC 62262
Supply voltage
Option 230 V Nominal range AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Power consumption max. 4,5 VA / 2 W
Option 24 V Nominal range AC 24 V - 90 V (50/60Hz) or
DC 24 V - 90 V, 150 V CATIII
Power consumption max. 4,5 VA / 2 W
Operating range +-10% of nominal range
Internal fuse, not exchangeable Type T1A / 250 V DC / 277 V AC according to IEC 60127
Recommended overcurrent protection device for the
line protection (UL approval)
Option 230 V: 6 - 16 A (Char. B)
Option 24 V: 1 - 6 A (Char. B)
Recommendation for the maximum number of devices on a line circuit breaker:
Option 230 V: Line circuit breaker B6A: max. 4 devices / line circuit breaker B16A: max. 11 devices
Option 24 V: Line circuit breaker B6A: max. 3 devices / line circuit breaker B16A: max. 9 devices