www.janitza.com Item no. 33.03.146 from firmware release 2.07 Doc. no. 1.040.058.9 Power Analyser Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support tel. 0049 6441 9642-22 Fax 0049 6441 9642-30 E-mail: info@janitza.com Internet: http://www.janitza.
UMG 96RM-E Content General 4 Inspection on receipt 6 Scope of delivery – UMG 96RM-E (RCM) 7 Available accessories 7 Product description 8 Proper use 8 Performance characteristics – UMG 96RM-E 10 Measuring process 11 Operating concept 11 GridVis network analysis software 11 Connection variants 12 Mounting 13 Installation 15 Power supply 15 Measuring voltage 16 Current measurement via I1 to I4 22 Residual current measurement (RCM) via I5, I631 Temperature measurement input 33 RS485 interface 34 Ethernet inter
UMG 96RM-E Operating hours meter Serial number (Addr.
UMG 96RM-E General Comments on the operating manual Copyright We welcome your comments. In the event that anything in this operating manual seems unclear, please let us know and send us an EMAIL to: info@janitza.
UMG 96RM-E Instructions for use Please read the operating manual at hand as well as all other publications that must be drawn from for working with this product (in particular for the installation, operation or maintenance). Follow all safety regulations and warning information. If you do not follow the information, it can result in bodily injury and/or damage to the product.
UMG 96RM-E Concerning these operating instructions Inspection on receipt These operating instructions are a part of the product. • Read the operating instructions before using the device. • Keep the operating instructions throughout the entire service life of the product and have them readily available for reference. • Pass the operating instructions on to each subsequent owner or user of the product.
UMG 96RM-E Scope of delivery – UMG 96RM-E (RCM) Number 1 2 1 1 1 1 1 1 1 1 1 1 Part no. 52.22.004 52.22.251 33.03.145 51.00.116 10.01.818 10.01.828 10.01.820 10.01.835 10.01.833 10.01.807 10.01.808 08.01.505 Description UMG 96RM-E Mounting clips. Operating instructions. CD with following content.
UMG 96RM-E Product description Proper use The UMG 96RM-E is intended for the measurement and calculation of electrical parameters such as voltage, current, power, energy, harmonics etc. in building installations, on distribution units, circuit breakers and busbar trunking systems. The UMG 96RM-E is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed. Can be installed in any attitude.
UMG 96RM-E The UMG 96RM-E can be used in industrial and domestic settings. Device characteristics • Supply voltage: 230V (95V-240V AC) • Frequency range: 45-65Hz Device functions • 3 voltage measurements, 300V • 4 current measurements (via current transformers ../5A or ../1A) • 2 residual current measurements (via residual current transformers ..
UMG 96RM-E Performance characteristics – UMG 96RM-E General • Front panel integration device with dimensions 96x96 mm.
UMG 96RM-E Measuring process GridVis network analysis software The UMG 96RM-E measures continuously and calculates all effective values over a 9 period interval. The UMG 96RM-E measures the real effective value (TRMS) of the voltage and current connected to the measurement inputs. The UMG 96RM-E can be programmed and read out using the GridVis network analysis software included in the scope of deliverables. For this a PC must be connected to the UMG 96RM-E via a serial interface (RS485) or via Ethernet.
UMG 96RM-E Connection variants Connection of a UMG 96RM-E to a PC via a interface converter: UMG 96RM-E Direct connection of a UMG 96RM-E to a PC via Ethernet. (gedrehtes Patchkabel) (Twisted patch cable) UMG 96RM-E UMG 96RM-E (gedrehtes Patchkabel) Connection of a UMG 96RM via a UMG 96RM-E as a gateway. UMG 96RM-E UMG 96RM UMG 96RM (gedrehtes Patchkabel) (gedrehtes Patchkabel) 12 Connecting a UMG 96RM-E to a PC via Ethernet.
UMG 96RM-E Mounting Position of installation The UMG 96RM-E is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed. Mounting position To ensure adequate ventilation, the UMG 96RM-E must be installed vertically. There should be separation above and below of at least 50mm with 20mm space to the sides. Front panel section Cut-out size: 92+0.8 x 92+0.8 mm. Fig.
UMG 96RM-E Mounting The UMG 96RM-E is fixed using the mounting clips found on the side of the switch panel. Before inserting the device, they should be moved out of the way in a horizontal lever using a screwdriver, for example. Fig. side view UMG 96RM-E with mounting clips. Loosening the clips is done using a screwdriver and a horizontal lever effect. The fastening is then done when the device is pushed in an the clamps lock in place when the screws are tightened.
UMG 96RM-E Installation Power supply L The 96RM-E needs a supply voltage to operate. The supply voltage is connected on the rear of the device via terminal blocks. N Fuse Before connecting the supply voltage, ensure that the voltage and frequency correspond to the details on the ratings plate! The supply voltage must be connected through a UL/ IEC approved fuse (1A type C). m • If installed in a building, a disconnector or circuit-breaker must be provided for the supply voltage.
UMG 96RM-E Measuring voltage You can use the UMG 96RM-E to measure voltage in TN-, TT-, and IT systems. The voltage measurement in the UMG 96RM-E is designed for the overvoltage category 300V CAT III (rated impulse voltage 4 kV). In systems without N, the measurements which require an N are to a calculated N. L1 L1 277V/480V 50/60Hz L2 480V 50/60Hz L2 L3 L3 N PE Impedance V1 V2 V3 VN V2 V1 V3 VN Auxiliary power Fig. schematic diagram - measurements in three-phase 4-wire systems.
UMG 96RM-E Network nominal voltage Lists of networks and their nominal network voltages in which the UMG 96RM-E can be used. Three-phase, 4-wire systems with earthed neutral conductor. Three-phase, 3-wire systems, unearthed. UL-N / UL-L UL-L 66V / 115V 120V / 208V 127V / 220V 220V / 380V 230V / 400V 240V / 415V 260V / 440V 277V / 480V 66V 120V 127V 220V 230V 240V 260V 277V 347V 380V 400V 415V 440V 480V Maximum system nominal voltage Fig. table for network nominal voltages i.a.w.
UMG 96RM-E Voltage measurement inputs The UMG 96RM-E has three voltage measurement inputs (V1, V2, V3). L1 L2 Surge voltage The voltage measurement inputs are suitable for use in networks where overvoltages of overvoltage category 300V CATIII (rated impulse voltage 4kV) can occur. Frequency For the measurement and calculation of measured values, the UMG 96RM-E needs the network frequency. The UMG 96RM-E is suitable for measurements on systems in a frequency range from 45 to 65Hz.
UMG 96RM-E When connecting the voltage to be measured, the following must be observed: • A suitable isolation device must be fitted to disconnect and de-energise the UMG 96RM-E. • The isolation device must be placed in the vicinity of the UMG 96RM-E, be marked for the user and easily accessible. • Use a UL/IEC approved circuit breaker 10A (Type C) for the over-current protection and isolation device.
UMG 96RM-E Wiring diagrams, voltage measurement • 3p 4w (Addr. 509= 0), factory setting • 3p 4wu (Addr. 509 = 1) L1 L1 L2 L2 L3 N L3 N V1 V2 V3 Fig. System with three and neutral conductor. VN line V1 conductors • 3p 4u (Addr. 509 = 2) L1 L2 L3 L3 V3 VN Fig. System with three line conductors without neutral conductor. Measurements which require a N are based on a calculated N. 20 VN • 3p 2u (Addr. 509 = 5) L2 V2 V3 Fig. System with three line conductors and neutral conductor.
UMG 96RM-E • 1p 2w1 (Addr. 509 = 4) • 2p 4w (Addr. 509 = 3) L1 L1 L2 L3 N N V1 V2 V3 V1 VN Fig. The values obtained from the voltage measurement inputs V2 and V3 are taken to be null and not calculated. • 1p 2w (Addr. 509 = 6) V2 V3 VN Fig. System with uniform phase loading. The measured values for the voltage measurement input V2 are calculated. • 3p 1w (Addr. 509 = 7) L1 L1 L2 L3 L2 L1 L2 L3 V1 V2 V3 VN Fig. TN-C system with single-phase three-wire connection.
UMG 96RM-E Current measurement via I1 to I4 The UMG 96 RM-E is designed to have current transformers with secondary currents from ../1A and ../5A attached cia terminals I1-I4. The factory default for the current transformer ratio is 5/5A and must be adapted to the current transformer employed if necessary. Direct measurement without a current transformer is not possible using the UMG 96RM-E. Only AC currents can be measured - DC currents cannot.
m Caution! The UMG 96RM-E is not suitable for measuring DC voltages. C It is not necessary to configure a connection schematic for the I4 measurement input. N L3 L1 Earthing of current transformers! If a connection is provided for the earthing of secondary windings then this must be connected to the earth. Load c L2 UMG 96RM-E Fig.
UMG 96RM-E Current direction The current direction can be individually corrected via the existing serial interface or on the device for each phase. If incorrectly connected, a subsequent re-connection of the current transformer is not required. When residual current measurements (RCM) are being carried out, there is no direction sensitive difference in the residual currents on the network or load side (not directionally sensitive).
UMG 96RM-E 25
UMG 96RM-E Wiring diagrams, current measurement (I1-I3) • 3p 4w (Addr. 510= 0), factory setting • 3p 2i (Addr. 510 = 1) L1 L1 L2 L2 L3 N L3 N I1 I2 I3 Fig. Measurement in a three-phase network with non-uniform load. • 3p 2i0 (Addr. 510 = 2) I1 • 3p 3w3 (Addr. 510 = 3) L1 L2 L2 L3 L3 I2 I3 Fig. The measured values for the current measurementinput I2 are calculated. 26 I3 Fig. System with uniform phase loading. The measured values for the current measurement input I2 are measured.
UMG 96RM-E • 3p 3w (Addr. 510 = 4) • 2p 4w (Addr. 510 = 5) L1 L1 L2 L2 L3 N L3 N I1 I2 I3 Fig. System with uniform phase loading. The measured values for the current measurement inputs I2 and I3 are calculated. • 1p 2i (Addr. 510 = 6) L1 I1 I2 I3 Fig. System with uniform phase loading. The measured values for the current measurement input I2 are calculated. • 1p 2w (Addr. 510 = 7) L1 L2 N I1 I2 I3 Fig.
UMG 96RM-E Wiring diagrams, current measurement (I1-I3) Ammeter • 3p 1w (Addr. 510 = 8) If you wish to measure the current not just using the UMG 96RM, rather also with a ammeter, the ammeter must be connected to the UMG 96RM-E in series. L1 L2 L3 L1 L2 L3 UMG 96RM I1 L1 L2 L3 1 2 A I1 I2 I3 Fig. 3 systems with uniform phase loading. The not connected measured values I2/I3, I1/I3 and I1/I2 of the respective systems are calculated.
UMG 96RM-E Total current measurement If the current measurement is done via two current transformers, the overall transformation ratio of the current transformers must be programmed into the UMG 96RM-E. The UMG 96RM-E must then be setup as follows: Primary current: 1000A + 1000A = 2000A Secondary current: 5A UMG 96RM I1 1 Einspeisung 1 Supply 1 1P1 (K) (L) 1P2 1S1 (k) (l) 1S2 Verbraucher A Consumer A P1 1S1 1S2 2 P2 2S1 2S2 Example: The current is measured via two current transformers.
UMG 96RM-E Analog inputs The UMG 96RM-E has 2 analog inputs which can be used for one residual current measurement or one temperature measurement. The measurement is done using terminals 32-34 (input 1) or 35-37 (input 2).
UMG 96RM-E Residual current measurement (RCM) via I5, I6 The UMG 96RM-E is for use as a residual current monitoring device (RCM), suitable for monitoring AC, pulsing DC, and DC. The UMG 96RM-E can measure residual currents in accordance with IEC/TR 60755 (2008-01) of type A and type B. C Residual current transformer ratio The GridVis software included with delivery can be used to individually program the residual current transformer inputs' transformer ratios.
UMG 96RM-E Connection example, residual current monitoring Residual current transformer L1 L2 L3 PEN N PE Fig. Example UMG96RM-E with residual current monitoring via measuring inputs i5/I6. Residual current transformer L1 L2 L3 N I1 I2 I3 I4 I5 M 3~ UMG 96RM-E (RCM) C 32 I6 I t i s n o t n e c e s s a r y t o c o n f i g u re a connection schematic for residual current inputs I5 and I6.
UMG 96RM-E Temperature measurement input The UMG 96RM-E has two temperature measuring inputs. The temperature is measured via terminals 32/34 (input 1) and 35/37 (input 2). Do not exceed the total resistance load (sensor + cable) of 4kOhm. PT100 PT100 m Use a shielded cable to connect the temperature sensor. Fig.
UMG 96RM-E RS485 interface Termination resistors In UMG 96RM-E, the RS485 interface is designed as a 2 pin plug contact, which communicates via the Modbus RTU protocol (also see Parameter programming). The cable is terminated with resistors (120Ohm, 1/4W) at the beginning and at the end of a segment. The UMG 96RM-E does not contain any termination resistors. Correct Incorrect A B RS485 interface, 2 pin plug contact Terminal strip in the cabinet. Device with RS485 interface.
UMG 96RM-E Screening Cable type Twisted screened cable should be used for connections via the RS485 interface. The cable used must be suitable for an environmental temperature of at least 80°C. • Earth the screens of all cables that lead to the cabinet, upon entering the cabinet. • Connect the screens over a generous area and in a manner that will conduct well, to a low-noise earth. • Gather the cables mechanically above the earthing clamp in order to avoid damage due to cable movements.
UMG 96RM-E Bus structure • All devices are connected in a bus structure (line) and each device has its own address within the bus (see also Parameter programming). • Up to 32 subscribers can be connected together in a single segment. • The cable is terminated with resistors (bus termination 120Ohm, 1/4W) at the beginning and at the end of a segment. • With more that 32 subscribers, repeaters (amplifiers) must be used to connect the individual segments.
UMG 96RM-E Ethernet interface The Ethernet network settings should be specified by the network administrator and set on UMG 96RM-E accordingly. If the network settings are not known, the UMG 96RME may not be integrated into the network through the patch cable. m m Ethernet Connection PC / Switch Caution! Connection of the UMG96RM-E to the Ethernet may only be carried out after discussion with the network administrator! Caution! The UMG 96RM-E is factory-programmed for the fixed IP address 192.168.0.
UMG 96RM-E Digital in-/outputs The UMG 96RM-E has 2 digital outputs and 3 optional digital inputs or outputs, which are divided into two groups (see figure). This means that only entire group 2 (connection 28 to 31) operate either as input or output; a different allocation within the group is not possible! The status of the inputs or outputs of Group 2 is signalled via the corresponding LED (see LED status bar).
UMG 96RM-E DC connection example External Auxiliary voltage UMG 96RM-E Group 1: 13 C Digital Ouput 2 14 - + 15 28 When using the digital outputs as pulse outputs the auxiliary voltage (DC) must have a max. residual ripple of 5%. DC Digital Ouput 3 Digital Ouput 4 Digital Ouput 5 29 K1 Functions for the digital outputs can be adjusted clearly in the GridVis software provided in the scope of deliverables.
UMG 96RM-E Digital inputs When allocating Group 2 as inputs, the UMG96 RM-E has three digital inputs to each of which you can connect one signal transducer. When a signal is present, the corresponding LED lights up green. An input signal is detected on a digital input if a voltage of at least 10V and maximum 28V is applied and where a current of at least 1mA and maximum 6mA flows at the same time. Wiring longer than 30m must be screened.
UMG 96RM-E S0 pulse input You can connect an S0 pulse DIN EN62053-31 to any digital input. transducer per This requires an auxiliary voltage with an output voltage in the range 20 .. 28V DC and a resistor of 1.5kOhm. External Auxiliary voltage 24V DC - UMG 96RM-E Digital inputs 1-4 + 28 1.5k 2k21 2k21 2k21 2k21 2k21 2k21 29 Digital Input 1 S0 pulse transducer 30 Digital Input 2 31 Digital Input 3 2k21 Fig. Example for the connection of an S0 pulse transducer to digital input 1.
UMG 96RM-E The different statuses of the inputs and outputs are displayed via the LED status bar on the rear of the device. Digital inputs The LED assigned to a respective input lights up green when a signal of at least 1mA flows on this interface. Digital outputs The LED assigned to a respective output lights up red when the output is set as enabled - regardless of whether there is a continuing connection to this interface.
UMG 96RM-E 43
UMG 96RM-E Operation Programming mode The UMG 96RM-E is operated via buttons 1 and 2 with the following functions: • briefly pressing button 1 and 2: next step (+1) • pressing and holding button 1 and 2: previous step (-1) Measured values and programming data are displayed on an LCD display. You can view and change the necessary settings of the UMG 96RM-E in programming mode. Press button 1 and 2 simultaneously for about 1 second to switch to programming mode after entering the password.
UMG 96RM-E Max. value, HT/reference Min.
UMG 96RM-E Parameters and measured values Parameter indication example All necessary parameters for the use of UMG 96RM-E, such as current transformer data and frequently required measured values are provided in the table. Use the UMG 96RM‑E buttons to retrieve the contents of most of the addresses via serial interface. In this example, the contents of address "000" is indicated by the value "001" on display of the UMG 96RM‑E.
UMG 96RM-E Button functions Display mode Programming mode Select mode Select mode Password simultaneously simultaneously Scroll Scroll short short Measured value A(+1) ... long long Measured value A(-1) long Programming menu +1 Measured value B ... Program short For an overview of the measured value indications, see chapter "Overview of measured value indications".
UMG 96RM-E Configuration Connecting the supply voltage The supply voltage must be connected the configuration of the UMG 96RM-E . for The level of the supply voltage for the UMG 96RM‑E is specified on the rating plate. If no display appears, check whether the operating voltage lies within the nominal voltage range. Current and voltage transformers When the device is delivered, a current transformer ratio of 5/5A is entered.
UMG 96RM-E C Current and voltage transformers The GridVis software included with delivery can be used to individually program the current and voltage transformer input transformer ratios. Only the transformer ratio of the respective group of the current inputs I1-I3 and the voltage measurement inputs V1-V3 can be adjusted on the device. The transformer ratio of the current transformer input I4 and the residual current transformer inputs I5, I6 should be set in the GridVis software. Fig.
UMG 96RM-E Programming the current transformer for I1 to I3 Switch to the programming mode • Press button 1 and 2 simultaneously to switch to the programming mode. If a user password was programmed, the password menu appears in display with the indication „000“. The first digit of the user password is flashing and can be changed by pressing button 2. Press button 2 to select the next digit while it is flashing.
UMG 96RM-E Programming the voltage transformer • Select in the programming mode as described. The symbols for the programming mode PRG and the current transformer mode CT appear on the display. • Press button 2 to go to the voltage transformer settings. • Press button 1 to confirm the selection. • The first digit of the input field for the primary voltage is flashing.
UMG 96RM-E Programming parameters Switch to the programming mode • Select in the programming mode as described. The symbols for the programming mode PRG and the current transformer mode CT appear on the display. • Press button 2 to go to the voltage transformer settings. Press button 2 repeatedly to view the first parameter in the list. Changing parameters • Press button 1 to confirm the selection. • The last selected address and the corresponding value is indicated.
UMG 96RM-E TCP/IP configuration Description Within an Ethernet, each device has a unique TCP / IP address that can be assigned manually or from a DHCP server. The 4-byte device address (0 to 3 byte) can be extended in the TCP / IP configuration using the subnet mask and gateway data. Setting the TCP / IP device address (addr) manually • Select in the programming mode as described. The symbols for the programming mode PRG and the current transformer mode CT appear on the display.
UMG 96RM-E Manual setting of the subnet mask (SUb) • When in the programming mode, press button 2 to get to the subnet mask settings (SUb display). • Use button 1 to select the desired digit and set it by pressing button 2. Repeat this step for each digit in bytes 0 to 3 in a way similar to setting the TCP / IP device address. • After repeated display of byte 0 (no digit is flashing) one can set the gateway address.
UMG 96RM-E m Fig. Subnet mask (Sub), byte 0, value 255 C Caution! Connection of the UMG96RM-E to the Ethernet may only be carried out after discussion with the network administrator! The UMG 96RM-E is factory-programmed for the fixed IP address 192.168.0.123. Fig. Gateway (GAt), byte 0, value 192 Fig. Enabled dynamic allocation (dYn IP) of the TCP / IP address Fig.
UMG 96RM-E RS485 device address (Addr. 000) RS485 baud rate (Addr. 001) If multiple devices are connected to each other via the RS485 interface, a master device can only identify the devices by their device address. Within a network, each device must have its own device address. Addresses can be set in the range of 1 to 247. A common baud rate can be adjusted for the RS485 interfaces. The baud rate must be uniform for all devices on the network.
UMG 96RM-E MODBUS gateway (Addr. 002) User password (Addr. 050) Set address 002 as described in the table below to use the UMG 96RM-E Modbus Gateway function: A user password can be programmed to prevent accidental change of the programming data. Changes in the programming menu below can only be made after entering the correct user password. User password is not factory-programmed. In this case, the password menu is skipped and you get directly to the current transformer menu.
UMG 96RM-E Parameter Averaging method Mean value The applied exponential messaging method reaches at least 95% of the measurement value once the reporting time has run its course. Mean values are averaged over an adjustable period for the current, voltage and power measured values. The mean values are indicated by a bar over the measured value. The averaging time can be selected from a list with 9 fixed averaging times. Averaging time, current (Addr. 040) Averaging time, power (Addr.
UMG 96RM-E Min. and max. values Energy meter All measured values are measured and calculated during all 9 periods. Minimum and maximum values are determined for most measured values. The min. value is the smallest measured value determined since the last deletion. The max. value is the highest measured value determined since the last deletion. All minimum and maximum values are compared with the corresponding measured values and overwritten when exceeded or fallen short of.
UMG 96RM-E Mains frequency (Addr. 034) In order to determine the mains frequency automatically, a voltage L-N of greater than 10Veff must be applied to at least one of the voltage measurement inputs. The sampling frequency is computed for the current and voltage inputs based on the mains frequency. If the test voltage is missing, neither the network nor the sampling frequency can be computed. An acknowledgeable error message "500" will be displayed.
UMG 96RM-E Harmonics Total harmonic distortion THD Harmonics are integer multiples of a fundamental oscillation. The fundamental oscillation of the voltage for UMG 96RM-E must range between 45 and 65Hz. The calculated harmonic voltages and currents relate to this fundamental oscillation. Harmonics up to 40 times the fundamental frequency are detected. THD is the ratio of the rms value of the harmonics to the rms value of the fundamental oscillation.
UMG 96RM-E Measured value rotation Rotation time (Addr. 039) All 9 periods the measured values are calculated and the readings are displayed on a per second basis. There are two ways to retrieve the measurement readings: Setting range : 0 .. 60 seconds If 0 seconds are set, the measured value indications selected will not be rotated. The rotation time set applies to all display rotation profiles.
UMG 96RM-E Display profile (Addr. 037) Setting range: 0 .. 3 0 - Display profile 1, default value. 1 - Display profile 2, default value. 2 - Display profile 3, default value. 3 - Display profile, customizable. C C The customizable profiles (display rotation profile and display profile) can only be programmed using the GridVis software. Profile setting Both profiles (display rotation profile and display profile) are illustrated in the GridVis software included in the delivery package.
UMG 96RM-E Reset energy meter (Addr. 507) Phase sequence The real, apparent and reactive energy meters can only be reset simultaneously. The voltage phase sequence and the phase L1 frequency are displayed on the screen. Set "001" for address 507 to reset the energy meter. The phase sequence shows the three-phase system sequence. The rotary field usually rotates to the "right". The voltage measurement input phase sequence is checked and displayed in the UMG 96RM-E.
UMG 96RM-E LCD contrast (Addr. 035) Time recording The preferred view for the LCD display is from "below". The LCD display contrast can be adapted by the user. The contrast can be set stepwise in the range from 0 to 9. The UMG 96RM-E records the operating hours and the overall runtime of each comparator, 0 = very bright 9 = very dark • where the operating period is measured and displayed in hours with a resolution of 0.
UMG 96RM-E Operating hours meter Serial number (Addr. 754) The operating hours meter measures the UMG 96RM-E recording and displaying time. The operating period is measured and displayed in hours with a resolution of 0.1 h. The operating hours meter cannot be reset. The serial number displayed by the UMG 96RM-E consists of 6 digits and is a part of the serial number given on the rating plate. The serial number cannot be changed.
UMG 96RM-E Recordings 2 recordings are preconfigured in the default factory setting of the UMG 96RM-E. Recordings can be adjusted and extended via GridVis. • The min. recording time base is 1 minute. • Maximum 4 recordings, each with 100 measured values, are possible.
UMG 96RM-E Putting into service Applying the measuring-circuit voltage Connecting the supply voltage The UMG 96RM-E is designed for the connection of .. /1A and .. /5A current transformers. Only AC currents can be measured via the current measurement inputs - DC currents cannot. Short circuit all current transformer outputs except for one. Compare the currents displayed by the UMG 96RM with the applied current.
UMG 96RM-E Applying the residual current Phase sequence Connect residual current transformer only to the I5 and I6 inputs with a rated current of 30mA! Both residual current inputs can measure AC currents, pulsing direct currents and DC currents. Check the direction of the voltage rotating field in the measured value display of the UMG 96RM‑E. A “right” rotating field usually exists.
UMG 96RM-E Checking the measurement Checking the total power outputs If all voltage and current inputs are correctly connected, the individual and cumulative outputs are computed and displayed correctly. If all voltages, currents and outputs for the respective outer conductors are correctly displayed, the total power outputs measured by the UMG 96RM must also be correct.
UMG 96RM-E RS485 interface The MODBUS RTU protocol with CRC check on the RS485 interface can be used to access the data from the parameter and the measured value lists. Address range: 1 .. 247 Factory default setting: 1 The device is factory set to address 1 and the baud rate of 115,2 kbps. C C Broadcast (address 0) is not supported by the device. The message length must not exceed 256 bytes.
UMG 96RM-E Example: Reading the L1-N voltage The L1-N voltage is saved in the measured value list at address 19000. The L1-N voltage is available in the INT format. Address = 01 is approved as the UMG 96RM-E device address. The Query Message appears as follows: The Response of the UMG96 RM-E can appear as follows: Description Device address Function Start Addr. Hi Start Addr. Lo Ind. Value Hi Ind.
UMG 96RM-E Digital outputs The UMG 96RM-E features two digital outputs in group 1. Three further outputs can be used in group 2. The User can allocate different functions to the digital outputs The functions can be programmed by using the configuration menu of the GridVis software. + = - S2 S3 K3 K4 K5 - - 24V = DC + = + K1 13 S1 14 K2 15 Group 11 Gruppe 28 29 30 Fig.: Software GridVis, configuration menu 31 Group 2 2 Gruppe Digital inputs/outputs Digital-Eingänge/Ausgänge Fig.
UMG 96RM-E Digital outputs - Status displays The status of the switching outputs of group 1 is indicated by circular symbols in the display of the UMG 96RM-E. Group 1 Status digital output 1 Status digital output 2 Digital output stati The current flow can be <1mA. Digital output 1: Addr. 608 = 0 Digital output 2: Addr. 609 = 0 The current flow can up to 50mA. Digital output 1: Addr. 608 = 1 Digital output 2: Addr.
UMG 96RM-E Impulse output The digital outputs can be used for the output of pulses for the computation of power consumption. For this purpose, a pulse of defined length is applied on the output after reaching a certain, adjustable amount of power. You need to make various adjustments in the software GridVis (configuration menu) to use a digital output as a pulse one. • • • • • Digital output, Selection of source, Selection of measured value, Pulse length, Pulse value. Fig.
UMG 96RM-E Pulse length The pulse length applies to both pulse outputs and is set by the software GridVis. The typical pulse length of S0 pulse is 30ms. Pulse interval The pulse interval is at least as large as the selected pulse length. The pulse interval depends on the measured power, for example, and can take hours or days. Pulse length 10ms ..
UMG 96RM-E Pulse value The pulse value is used to indicate how much energy (Wh or varh) should correspond to a pulse. The pulse value is determined by the maximum connected load and the maximum number of pulses per hour. If you check the pulse value with a positive sign, the pulses will only be emitted when the measured value has a positive sign. If you check the pulse value with a negative sign, the pulses will only be produced when the measured value has a negative sign. Pulse value = C C max.
UMG 96RM-E Determine the pulse value External 230V AC operating voltage Set the pulse length Set the pulse length in accordance with the requirements of the connected pulse receiver. At a pulse length of 30 ms, for example, the UMG96RM generates a maximum number of 60,000 pulses (see Table "maximum number of pulses" per hour.
UMG 96RM-E Comparators and monitoring threshold values Five comparator groups (1-5) and 10 comparators per group (A – J) can be selected in order to monitor/control the thresholds. The results of the comparators A to J can be linked with AND or OR operators The result of the AND and OR operator can be allocated to the respective digital output. Fig.
UMG 96RM-E Service and maintenance Service The device is subjected to several different safety tests before leaving the factory and is labelled with a seal. If a device is opened then the safety checks must be repeated. Warranty claims will only be accepted if the device is unopened. Should questions arise, which are not described in this manual, please contact the manufacturer directly.
UMG 96RM-E Firmware update Battery If the device is connected to a computer via Ethernet, then the device firmware can be updated via the GridVis software. The internal clock is fed from the supply voltage. If the supply voltage fails then the clock is powered by the battery. The clock provides date and time information, for the records, min. and max. values and results, for example. Select a suitable update file (menu Extras / Update device) and the device and the new firmware will be transferred.
UMG 96RM-E Battery monitoring function The device indicates the condition of the battery via the "EEE" symbol followed by "bAt" and the status number. Depending on the status number a confirmation of the information by the operator may be required. It is recommended that the battery be replaced.
UMG 96RM-E Replacing the battery If the battery capacity is shown as < 75 %, we recommend that the battery be replaced. Procedure 1. Disconnect system and device from power supply before beginning work. 2. Discharge any electrostatic charge in your body, e. g. by touching an earthed cabinet or metal part (radiator) connected to the earth of the building. 3. Remove the battery from the battery compartment, —e.g. using long-nose pliers—.
UMG 96RM-E Error/warning messages Warnings The UMG 96RM-E can display four different error messages: Warnings are minor errors that can be acknowledged by buttons 1 or 2. The measured values continue to be retrieved and displayed. This error is displayed after each voltage return. • • • • warnings, clock/battery errors, fatal errors and overranges. In the case of warnings and fatal errors, the error message is followed by the "EEE" symbol and an error number. Fig.
UMG 96RM-E Clock/battery errors Clock or battery errors are displayed together with the "EEE" symbol followed by "bAt" and a status number. For a more detailed description please refer to "Baterry control function" and "Replacing the battery". Fig. Clock / battery error number 330 (clock does not run and has to be set. Major errors When a major error occurs, the device must be sent to the manufacturer's service center for inspection and adjustment.
UMG 96RM-E Overranges Overranges are displayed as long as they exist and cannot be acknowledged. An overrange exists if at least one of the four voltage or current measurement inputs lies outside their specified measuring range. The "upwards" arrow indicates the phase (L1-L3) where the overrrange occured. The appropriate error message for current path I4 is generated as shown below. The “V” and “A” symbols indicate whether the overrange occurred in the current or in the voltage path.
UMG 96RM-E Parameter overrange A detailed description of the error is coded in the parameter overrange (Addr.
UMG 96RM-E Procedure in the event of faults Possible fault Cause Remedy No display External fusing for the power supply voltage has tripped. Replace fuse. No current display Measurement voltage is not connected. Connect the measuring-circuit voltage. Measurement current is not connected. Connect measuring-circuit current. Current measurement in the wrong phase. Check connection and correct if necessary. Current transformer factor is incorrectly programmed.
UMG 96RM-E Possible fault Effective power too large or too small. An output is not responding. Cause Read out and program the current transformer transformation ratio at the current transformer The current path is assigned to the wrong voltage path. Check connection and correct if necessary. The programmed voltage transformer transformation ratio is incorrect. Read out and program the voltage transformer transformation ratio at the voltage transformer. The output was incorrectly programmed.
UMG 96RM-E Technical data General information Net weight (with attached connectors) approx. 370g Packaging weight (including accessories) approx. 950g Device dimensions Approx. w = 96mm, h = 96mm, d = 78mm Battery Lithium battery CR2032, 3V (approval i.a.w. UL 1642) Service life of background lighting 40000h (after this period of time the background lighting efficiency will reduce by approx.
UMG 96RM-E Ambient conditions during operation The UMG 96RM is intended for weather-protected, stationary use. Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1). Operating temperature range K55 (-10°C .. +55°C) Relative humidity 0 to 75 % RH Operating altitude 0 .. 2000m above sea level Degree of pollution 2 Mounting position any Ventilation Forced ventilation is not required. Protection against ingress of solid foreign bodies and water - Front side - Rear side IP40 i.a.w.
UMG 96RM-E Digital outputs 2 and 3 optional digital outputs, semiconductor relays, not short-circuit proof. Switching voltage max. 33V AC, 60V DC Switching current max. 50mAeff AC/DC Response time 9 periods + 10ms * Pulse output (energy pulse) max. 50Hz * Response time e.g. at 50Hz: 180ms + 10ms = 190 ms Digital inputs 3 optional digital outputs, semiconductor relays, not short-circuit proof. Maximum counter frequency 20Hz Input signal present 18V ..
UMG 96RM-E Temperature measurement input 2 optional inputs. Update time 1 second Connectable sensors PT100, PT1000, KTY83, KTY84 Total burden (sensor + cable) max. 4 kOhm Sensor type Temperature range Resistor range Uncertainty in measurement KTY83 -55°C ... +175°C 500Ohm ... 2,6kOhm ± 1,5% rng KTY84 -40°C ... +300°C 350Ohm ... 2,6kOhm ± 1,5% rng PT100 -99°C ... +500°C 60Ohm ... 180Ohm ± 1,5% rng PT1000 -99°C ... +500°C 600Ohm ...
UMG 96RM-E Serial interface RS485 - Modbus RTU/Slave 9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps Stripping length 7mm Measuring voltage 1) Three-phase 4-conductor systems with nominal voltages up to 277V/480V (+-10%) Three-phase 3-conductor systems, unearthed, with nominal voltages up to IT 480V (+-10%) Overvoltage category 300V CAT III Measurement surge voltage 4kV Measurement range L-N 01) .. 300Vrms (max. surge voltage 520Vrms ) Measurement range L-L 01) .. 520Vrms (max.
UMG 96RM-E Current measurement I1 - I4 Measurement range 0 .. 5Arms (maximum overload 7 arms) Crest factor 1.98 Resolution 0.1mA (Display 0.01A) Overvoltage category 300V CAT II Measurement surge voltage 2kV Power consumption approx. 0.2 VA (Ri=5mOhm) Overload for 1 sec. 120A (sinusoidal) Sampling frequency 20kHz Residual current measurement I5 / I6 Rated current 30mArms Rated current 40mArms Operating current 50µA Resolution 1µA Crest factor 1.
UMG 96RM-E Terminal connection capacity: power supply voltage, voltage and current measurement Conductors to be connected. Only one conductor can be connected per terminal! Single core, multi-core, fine-stranded 0.2 - 2.5mm2, AWG 24-12 Terminal pins, core end sheath 0.25 - 2.5mm2 Tightening torque 0.5 - 0.6Nm Stripping length 7mm Terminal connection capacity: Residual current or temperature measurement inputs and digital inputs / outputs Rigid/flexible 0.14 - 1.
UMG 96RM-E Ethernet connection Connection RJ45 Functions Modbus gateway, embedded web server (HTTP) Protocols TCP/IP, DHCP-Client (BootP), Modbus/TCP (Port 502), ICMP (Ping), NTP, Modbus RTU over Ethernet (Port 8000), FTP, SNMP 97
UMG 96RM-E Function parameters Function Symbol Precision class Measurement range Display range Total effective power P 0.55) (IEC61557-12) 0 .. 5.4 kW 0 W .. 9999 GW * Total reactive power QA, Qv 1 (IEC61557-12) 0 .. 5.4 kvar 0 varh .. 9999 Gvar * Total apparent power SA, Sv 0.55) (IEC61557-12) 0 .. 5.4 kVA 0 VA .. 9999 GVA * Total active energy Ea 0.55) (IEC61557-12) 0 .. 5.4 kWh 0 Wh .. 9999 GWh * Total reactive power ErA, ErV 1 (IEC61557-12) 0 .. 5.4 kvarh 0 varh ..
UMG 96RM-E Function Symbol Precision class Measurement range Display range Current harmonics Ih Kl. 1 (IEC61000-4-7) up to 2.5 kHz 0 A .. 9999 kA THD of the current 3) THDi 1.0 (IEC61557-12) up to 2.5 kHz 0 % .. 999 % THD of the current 4) THD-Ri - - - Mains signal voltage MSV - - - 1) Referred to amplitude. 2) Referred to phase and amplitude. * The display returns to 0 W when the maximum total energy values are reached. 5) Accuracy class 0.5 with ../5 A transformer.
UMG 96RM-E Parameter and modbus address list The following excerpt of the parameter list provides the settings that are necessary for the proper operation of the UMG 96RM-E, such as current transformer and device addresses. The valuesin the parameter list can be set and read. C The excerpt of the measured value list includes the measured and calculated values, output status data and recorded values to be read.
UMG 96RM-E Address format RD/WR Unit Note 20 FLOAT RD/WR A Current transformer I2, sec. 22 FLOAT RD/WR V Voltage transformer V2, prim. 24 FLOAT RD/WR V Voltage transformer V2, sec. 26 FLOAT RD/WR A Current transformer I3, primary 28 FLOAT RD/WR A Current transformer I3, sec. 30 FLOAT RD/WR V Voltage transformer V3, prim. 32 FLOAT RD/WR V Voltage transformer V3, sec. 34 SHORT RD/WR Hz Frequency estimation 0=Auto, 45 ..
UMG 96RM-E Address 50 format RD/WR Unit Note Adjustment range Default SHORT RD/WR - Password 0 .. 999 0 (No password) 0..32000 0 0..
UMG 96RM-E Address format RD/WR Unit Note Adjustment range 512 513 514 515 516 517 SHORT SHORT SHORT SHORT SHORT SHORT RD/WR RD/WR RD/WR RD/WR RD/WR RD/WR - Year Month Day Hour Minute Second 0..99 0..12 0..31 0..24 0..59 0..59 600 UINT RD/WR - Overrange 0..0xFFFFFFFF 750 754 756 SHORT SERNR SERNR RD RD RD - Software release Serial number Production no. C Default *2 *2 *2 *2 *2 *2 Only the first 3 digits (###) of a value are displayed on the screen.
UMG 96RM-E Table 2 - Modbus address list (frequently needed measured values) C The addresses contained in the description can be adjusted directly on the device in the range from 0 to 999. The address range above 1000 can only be processed via modbus! C A complete overview of the parameters and measured values as well as explanations regarding the selected measured values is filed in the document “Modbus Address List” on the CD or Internet.
UMG 96RM-E Modbus address Address via Display Format RD/WR Unit Note 19036 19038 19040 19042 19044 19046 19048 19050 19052 19054 19056 19058 19060 19062 19064 19066 19068 19070 19072 19074 19076 19078 19080 19082 19084 19086 19088 19090 19092 19094 19096 876 878 880 882 820 822 824 800 - float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float RD RD RD RD RD RD RD RD RD R
UMG 96RM-E Modbus address Address via Display Format RD/WR Unit Note 19098 19100 19102 19104 19106 19108 19110 19112 19114 19116 19118 19120 836 838 840 908 910 912 float float float float float float float float float float float float RD RD RD RD RD RD RD RD RD RD RD RD varh varh varh varh varh varh % % % % % % Reactive energy, inductive, L3 Reactive energy L1..L3, ind. Reactive energy, capacitive, L1 Reactive energy, capacitive, L2 Reactive energy, capacitive, L3 Reactive energy L1..L3, cap.
UMG 96RM-E 107
UMG 96RM-E Dimension diagrams All dimensions provided in mm Rear view View from below □ 91,5 110,5 108
UMG 96RM-E Side view Cut-out size ca.
UMG 96RM-E Measured value displays overview A01 B01 C01 D01 Measured values L1-N voltage L2-N voltage L3-N voltage Mean values L1-N voltage L2-N voltage L3-N voltage Max. values L1-N voltage L2-N voltage L3-N voltage Min. value L1-N voltage L2-N voltage L3-N voltage A02 B02 C02 D02 Measured values L1-L2 voltage L2-L3 voltage L3-L1 voltage Mean values L1-L2 voltage L2-L3 voltage L3-L1 voltage Max. values L1-L2 voltage L2-L3 voltage L3-L1 voltage Min.
UMG 96RM-E A08 B08 C08 Measured value Sum Apparent power Mean value Sum Apparent power Max. value Sum Apparent power A09 B09 C09 Measured values L1 reactive power L2 reactive power L3 reactive power Mean values L1 reactive power L2 reactive power L3 reactive power Max. values (ind) L1 reactive power L2 reactive power L3 reactive power A10 B10 C10 Measured value Reactive power sum Mean value Reactive power sum Max.
UMG 96RM-E A15 Measured value L1 cos(phi) L2 cos(phi) L3 cos(phi) A16 B16 Measured value Sum cos(phi) Mean value Sum cos(phi) A17 Measured value Frequency L1 Rotary field indication A18 Measured value Total active energy (without backstop) B18 C18 D18 Measured value Total active energy (Consumption) Measured value Total active energy (Supply) Measured value Sum Apparent energy A19 B19 C19 Measured value (ind) Reactive power Measured value Sum Reactive power cap.
UMG 96RM-E A22 B22 H22 Measured value 1. Harmonics U L2 Measured value 3. Harmon. U L2 ... Measured value 15. Harmon. U L2 A23 B23 H23 Measured value 1. Harmonics U L3 Measured value 3. Harmon. U L3 ... Measured value 15. Harmon. U L3 A24 B24 H24 Measured value 1. Harmonics I L1 Measured value 3. Harmon. I L1 ... Measured value 15. Harmon. I L1 A25 B25 H25 Measured value 1. Harmonics I L2 Measured value 3. Harmon. I L2 ... Measured value 15. Harmon. I L2 ... Measured value 15.
UMG 96RM-E A29 B29 H29 Max. value 1. Harmonics U L3 Max. value 3. Harmonics U L3 ... Max. value 15. Harmonics U L3 A30 B30 H30 Max. value 1. Harmonics I L1 Max. value 3. Harmonics I L1 ... Max. value 15. Harmonics I L1 A31 B31 H31 Max. value 1. Harmonics I L2 Max. value 3. Harmonics I L2 ... Max. value 15. Harmonics I L2 ... Max. value 15. Harmonics I L3 A32 Max. value 1.
UMG 96RM-E 115
UMG 96RM-E Declaration of conformity The UMG 96RM fulfils the safety requirements of: Directive 2004/108/EC in conjunction with DIN EN61326-1:2011 (IEC 61326-1:2010) as well as the Directive 2006/95/EC in conjunction with DIN EN 61010-1:2011 (IEC 61010-1:2011) and DIN EN 61010-2-030:2011 (IEC 61010-2-030:2011) Standards taken into consideration: Immunity from interference DIN EN 61326-1:2006 (IEC 61326-1:2005) Electrical equipment for measurement, control, and laboratory use EMC requirements - Part
UMG 96RM-E Connection example 1 (with residual current measurement IPE / IRES) + = S1 S2 S3 IPE IDIFF B - = + 13 K3 K2 14 15 Group 11 Gruppe 28 29 0-30 mA K5 K4 30 31 32 Group 2 Gruppe 2 A 0-30 mA 33 34 I5 35 36 16 B 37 I6 RS485 Analog inputs Analog-Eingänge Digital inputs/outputs Digital-Eingänge/Ausgänge 17 A Ethernet 10/100Base-T K1 UMG 96RM-E (RCM) Power supply Versorgungsvoltage spannung Measuring voltage Spannungsmessung N/- L/+ V1 V2 V3 VN 1 3 4 5 6 2
UMG 96RM-E Connection example 2 (with temperature and residual current measurement) + = S3 IDIFF B PT100 = + K1 K3 K2 14 15 28 29 30 31 Group 2 Gruppe Group 1 Gruppe A 0-30 mA K5 K4 32 33 34 I5 35 36 16 B 37 I6 RS485 Analog inputs Analog-Eingänge Digital inputs/outputs Digital-Eingänge/Ausgänge 17 A UMG 96RM-E (RCM) Power supply Versorgungsvoltage spannung Measuring voltage Spannungsmessung N/- L/+ V1 V2 V3 VN 1 3 4 5 6 2 1) 2) 2) Current measurement Strommessung
UMG 96RM-E Basic functions quick guide Adjusting current transformer, primary current Adjusting the current transformer Switch to the programming mode: • Press button 1 and 2 simultaneously for around 1 second to switch to the programming mode. The symbols for the programming mode PRG and the current transformer mode CT appear on the display. • Press button 1 to confirm the selection. • The first digit of the input field for the primary current is flashing.
UMG 96RM-E TCP/IP addressing quick guide Manual TCP/IP settings Switch to the programming mode: • Press button 1 and 2 simultaneously for around 1 second to switch to the programming mode. The symbols for the programming mode PRG and the current transformer mode CT appear on the display. Adjust the TCP/IP address (Adr.) • Press button 2 to select "Adr" • Press button 1 to enable the first digit (byte 0) of the address (digit is flashing). Press button 2 to set the digit.