User manual
UMG 96RM-E
35
Modbus-Adressenliste
Adresse Format RD/WR Einheit Bemerkung Index
Maxwerte der Mittelwerte, Type Short
4844 SHORT RD/WR mA Max.valueofaverageval.,CurrentIL [0]
4845 SHORT RD/WR mA Max.valueofaverageval.,CurrentIL [1]
4846 SHORT RD/WR mA Max.valueofaverageval.,CurrentIL [2]
4847 SHORT RD/WR mA Max.valueofaverageval.,Vectorsum;IN=I1+I2+I3 [3]
4848 SHORT RD/WR 100mW Max.valueofaverageval.,RealpowerPLN [0]
4849 SHORT RD/WR 100mW Max.valueofaverageval.,RealpowerPLN [1]
4850 SHORT RD/WR 100mW Max.valueofaverageval.,RealpowerPLN [2]
4851 SHORT RD/WR 100mW Max.valueofaverageval.,Sum;Psum3=P1+P2+P3 [3]
10864 SHORT RD/WR mA Max.valueofaverageval.,currentIL4,integer
11457 SHORT RD/WR °C Max.valueofaverageval.,Temperatureinput1,integer
11458 SHORT RD/WR °C Max.valueofaverageval.,Temperatureinput2,integer
11459 SHORT RD/WR % Max.valueofaverageval.,Diff14-20mA,integer
11460 SHORT RD/WR % Max.valueofaverageval.,Diff24-20mA,integer
11461 SHORT RD/WR A Max.valueofaverageval.,CurrentDiff1,integer
11462 SHORT RD/WR A Max.valueofaverageval.,CurrentDiff2,integer