Modbus-Adressenliste
Adresse Format RD/WR Einheit Bemerkung Index
932 FLOAT RD A Current,imaginarypartIL [0]
934 FLOAT RD A Current,imaginarypartIL [1]
936 FLOAT RD A Current,imaginarypartIL [2]
938 FLOAT RD - Rotationeld;1=right,0=none,-1=left
10085 FLOAT RD A CurrentIL4
10087 FLOAT RD % THDIL4
10089 FLOAT RD % TDDIL4
10091 FLOAT RD W Powers0,input1 [0]
10093 FLOAT RD W Powers0,input2 [1]
10095 FLOAT RD W Powers0,input3 [2]
10865 FLOAT RD °C Temperatureinput1
10867 FLOAT RD °C Temperatureinput2
10869 FLOAT RD % Diff14-20mA
10871 FLOAT RD % Diff24-20mA
10873 FLOAT RD A CurrentDiff1
10875 FLOAT RD A CurrentDiff2
10877 FLOAT RD % THDIDiff1
10879 FLOAT RD % THDIDiff2
11463 FLOAT RD A ArithmeticSumCurrent(I1+I2+I3)