User manual
UMG 96RM-E
18
Modbus-Adressenliste
Adresse Format RD/WR Einheit Bemerkung Index
VoreinstellungEinstellbereich
21136 SHORT RD/WR Digouttype,Sourceselectionfordigitaloutput5 0..4 0
0=Comparator3
1=Pulseoutput(S0)
2=Externalsource-Modbus
4=Externalsource-Ethernet
21137 SHORT RD/WR Dig.Output1inverted 0,1 0
21138 SHORT RD/WR Dig.Output2inverted 0,1 0
21139 SHORT RD/WR Dig.Output3inverted 0,1 0
21140 SHORT RD/WR Dig.Output4inverted 0,1 0
21141 SHORT RD/WR Dig.Output5inverted 0,1 0
21142 SHORT RD/WR Output1,Modbusremote,address 0,1 0
21143 SHORT RD/WR Output2,Modbusremote,address 0,1 0
21144 SHORT RD/WR Output3,Modbusremote,address 0,1 0
21145 SHORT RD/WR Output4,Modbusremote,address 0,1 0
21146 SHORT RD/WR Output5,Modbusremote,address 0,1 0