Modbus-Adressenliste
Adresse Format RD/WR Einheit Bemerkung Index
3512 FLOAT RD s Systemuptime
10080 SHORT RD Statusdigitaloutput1 0,1
0=notactive,1=active
10081 SHORT RD Statusdigitaloutput2 0,1
0=notactive,1=active
10082 SHORT RD Statusdigitaloutput3 0,1
0=notactive,1=active
10083 SHORT RD Statusdigitaloutput4 0,1
0=notactive,1=active
10084 SHORT RD Statusdigitaloutput5 0,1
0=notactive,1=active
10109 SHORT RD Statusdigitalinput 0,1
0=notactive,1=aktive
10110 SHORT RD Statusdigitalinput 0,1
0=notactive,1=aktive
10111 SHORT RD Statusdigitalinput 0,1
0=notactive,1=aktive
10112 INT RD Overcurrentagi4
10114 SHORT RD Digitalinputs,bitcoded
11619 FLOAT RD/WR Ohm Resistancetempinput1
11621 FLOAT RD/WR Ohm Resistancetempinput2
20008 FLOAT RD/WR A CurrenttransformerI4,primary 0..1000000
(*2)
5
20010 FLOAT RD/WR A CurrenttransformerI4,secondary 1..5 5
20012 FLOAT RD/WR A CurrenttransformerI5,primary 0..1000000
(*2)
5
20014 FLOAT RD/WR A CurrenttransformerI5,secondary 1..5 5
20016 FLOAT RD/WR A CurrenttransformerI6,primary 0..1000000
(*2)
5
20018 FLOAT RD/WR A CurrenttransformerI6,secondary 1..5 5
20020 DATA 212 Record 1 configuration
20126 DATA 212 Record 2 configuration
20232 DATA 212 Record 3 configuration
20338 DATA 212 Record 4 configuration
20444 FLOAT RD/WR Multiplicationfactorfors0input1frequency
20446 FLOAT RD/WR Multiplicationfactorfors0input2frequency
20448 FLOAT RD/WR] Multiplicationfactorfors0input3frequency
20450 STRING RD/WR 32 Name of S0 input type IN1
20466 STRING RD/WR 32 Name of S0 input type IN2
20482 STRING RD/WR 32 Name of S0 input type IN3
20498 STRING RD/WR 32 Name of S0 input type IN1
20514 STRING RD/WR 32 Name of S0 input type IN2
20530 STRING RD/WR 32 Name of S0 input type IN3
20546 STRING RD/WR 100 Name of S0 input type IN1
20596 STRING RD/WR 100 Name of S0 input type IN2
20646 STRING RD/WR 100 Name of S0 input type IN3
20696 SHORT RD Pulseoutreferenceaddress
20697 SHORT RD Pulseoutreferenceaddress
20698 SHORT RD Pulseoutreferenceaddress
20699 SHORT RD Pulseoutreferenceaddress
20700 SHORT RD Pulseoutreferenceaddress
20701 FLOAT RD Pulsegenerationfactor(freq=val/fac)
20703 FLOAT RD Pulsegenerationfactor(freq=val/fac)
20705 FLOAT RD Pulsegenerationfactor(freq=val/fac)
20707 FLOAT RD Pulsegenerationfactor(freq=val/fac)
20709 FLOAT RD Pulsegenerationfactor(freq=val/fac)
21147 BYTE RD/WR Configuration tariff, active energy source [0]
21148 BYTE RD/WR Configuration tariff, active energy source [1]
21149 BYTE RD/WR Configuration tariff, active energy, source [2]
21150 BYTE RD/WR Configuration tariff, active energy, source [3]
21151 BYTE RD/WR Configuration tariff, active energy, source [4]
21152 BYTE RD/WR Configuration tariff, active energy, source [5]
VoreinstellungEinstellbereich
Parameter II