Treat vertical joints in HardiePanel
®
vertical siding by using one of the
following four methods:
1. Install the panels in
moderate contact.
2. Leave an appropriate gap
between panels (1/8 in. is the
most common), and caulk
using a high-quality paintable
caulk, that meets ASTM C-834
or C-920 requirements. (Not
recommended for ColorPlus)
Panels may be installed first with
caulk applied in the joints after
installation; or as an option, after
the first panel is installed, apply a
bead of caulk along the panel edge.
When the next panel is installed
against the first, the edge embeds
in the applied caulk creating a
thorough seal between the edges
of the panels.
3. Vertical joints may be covered
with wood or fiber-cement
batten strips. If James Hardie
®
siding or trim products are
ripped and used as batten
strips, paint or prime the cut
edges. Batten strips should
span the vertical joint by at least
¾
in. on each side.
4. Metal or PVC “H” moldings can
be used to join two sections of
HardiePanel siding.
The caulk joint method is
not recommended for the
ColorPlus
®
products
WARNING
!
VERTICAL JOINT TREATMENT
TIP: Stainless steel fasteners are
recommended when installing
James Hardie products.
6d
screw
4d
common
1
.113 in x .267 in x 1.5 in
ring shank
siding nail
5
.091 in. x .225 in x 1.5 in
roofing nail
9
No. 11ga 1.25 in long
ET&F
13
[AKN100-0150NA]
.100 in x .25 in x 1.5 in
2
.113 in x .267 in x 2 in
6d
common
Fastening
Substrate
Fastening Types
Approved Fastener
wood
studs
24 in o.c.
16 in o.c.
steel
studs
16 in o.c
or
24 in o.c.
Ribbed Bugle-Head No. 8 (.323 in x 1 in)
screw
7
3 Battened joint
4 H-Channel joint
1 Moderate contact joint
2 Caulked joint
Panels are butted together lightly.
1/8 in. gap left between
panels is lled with caulk.
(not applicable with ColorPlus)
HardieTrim
®
batten board covers
the joint between panels.
Note: The following outlines the recommended applications for ColorPlus and
Primed panels. Not all designs will be suitable for every application:
• Exposed fasteners or battens is the recommended application for ColorPlus products
• Do not use touch-up over fastener heads for smooth ColorPlus products - primed panel
recommended
• For ColorPlus panel applications that require fasteners in the eld, it is acceptable to
use touch-up over fasteners for Cedarmill and Stucco panel only, but correct touch-up
application is important. Some colors may show touch-up when applied over fasteners.
Trim is recommended to cover joints when appropriate.
A manufactured H-channel captures
the vertical edges of the panels.
12.3 12.4
12.612.5
HARDIEPANEL
SIDING FASTENER SPECIFICATIONS
The Fastener Specifications table shows fastener options for a variety of different nailing substrates. Please
refer to the applicable ESR report online (see back page) to determine which fastener meets your wind load
137
1
1 2 5 9
2 9