JA-63 „PROFI“ Alarm system - installation manual
Contents: 1 Architecture of the control panel ................................................................................................................................4 2 Control panel installation............................................................................................................................................4 2.1 Mains supply connection .......................................................................................................................................
This product should be installed by professional installers. The manufacturer assumes no liability for damages caused by incorrect installation or improper use of this system. 1 another JA-6x control panel can be enrolled as a subsystem (Master & Slave architecture). The master control panel receives information from the sub control panel and it can also arm and disarm the subsystem panel.
2.1 Mains supply connection It is specified to connect the control panel by a permanent twowire cable. The power supply has a double isolation. The ground wire is unattached. • • • 3 RADIO MODULE JA-63R An inlet is realized by a permanent two-wire cable with a double isolation – wire diameter 0.75 – 1.5 mm2. The inlet must be connected to the independent circuit breaker (10 A max) in the object, which has function of the switch.
+U (during an alarm, the charging will temporarily halt). The siren can also be used for arming and disarming chirps and as an audible indicator while in the testing mode (see section 10). PGX, PGY are outputs (switching to GND when activated, max. 12V, 100mA). The function of these outputs are determined by the setting in the programming mode (see 9.6). The control panel also wirelessly transmits the PGX and PGY signals and UC receiving units can be used as remote outputs for these signals.
• • 5 7 The JA-60 keypad(s) Back up battery installation There is a space for a size 12V, 1.3 or 2.6Ah battery (battery size should corresponding to a desired backup period). The control panel recharges and checks the condition of the back up battery. If the system is powered from the battery for an extended time and the battery is nearly discharged, the control panel will first trigger a technical alarm and then it will disconnect the battery to prevent damage.
List of control panel programmable parameters Function Enrolling of detectors and controllers Hard-wired zone input setting sequence options 1 60 nn xys factory note 1& 7 scroll, 2 erases item - R module nn - zone, x - triggering, y - reaction, s - section L1=delay L2=next d. L3=instant L4=tamper Exit delay 20x x = 1 to 9 (x 10sec.) 30sec. Entrance delay 21x x = 1 to 9 (x 10sec.) 30sec. Alarm duration 22x x = 1 to 8 (min.), 0=10s, 9=15min 4min.
.1 has no current communication with any other control panel (This protects you from enrolling your neighbor’s siren). • Multiple outdoor sirens or multiple subsystems enrolment – enter 000000 while in enrolling mode. After this outdoor sirens and JA-6x subsystems can be enrolled to positions 1 to 16 (position A and/or J must be used first). • By pressing the button 8 in the enrolment mode the communication quality of the items can be checked (LED indicator “battery” will start flashing).
9.3 Note: the control panel also wirelessly transmits the PgX and PgY signals. Wireless output modules UC-216 and UC-222 can be used to receive the signals (see 9.12). The function of the UC module output relays is determined by the 23x and 24x setting. Exit delay sequence: 2 0 x To change the duration of the exit delay enter: 20x (where x represents time in seconds x10). The delay can be selected from 10 to 90 seconds.
9.10 Reset enabled 9.12 sequence: 2 8 x Enrollment of the control panel to a UC-2xx or to a master control panel sequence: 2 9 9 The factory default reset (see 11) can be disabled. This way no unauthorized future programming of the control panel will be possible. The wireless control panel can send data to output modules UC–216, UC–222 and UC-260. It can also work as a subsystem of another JA-6x. options: Enter the enrolling mode of the UC receiving device and then enter 299 on the control panel.
9.16 Exit delay audible indication options: sequence: 3 3 x 3 7 1 alarm in disarm & partial arming enabled The exit delay can be indicated by the “beeping“ of the keypad (for the last five seconds, the beeping is faster). The audible indication can be disabled with this setting. 3 7 0 alarm in disarm & partial arming disabled Factory default setting: enabled options: 9.
9.24 Options: Only first source of alarm is recorded sequence: 691 x 6961 Communication loss causes an alarm When any item triggers the alarm 4 times in a row the system will bypass it until any other events occurs. But it is possible to set the limit at the incoming events so only the very first event during the entire alarm will be recorded. This function is useful especially if the system contains a GSM communicator in order to decrease quantity of the SMS messages.
where: nn = number of the enrolled controller from 01 to 08 (c1 to c8) s = section: 1 = A, 2 = B 9.36 sequence: 4 hh mm dd MM YY The control panel has a built in real time clock. All events are stored to the event memory including the time of the event. The clock should be set after the installation is completed.
User can check and operate the JA-63 system easily via their PC, can read complete events memory with all details, can view the map of the installation (seeing topical triggering of the detectors) etc. However, the user can not change settings of the system. Installer who has access rights can program the system, can check the communication quality of the items, can view the level of interference in the location etc.
13 Recommended professional staller basic rules • in- • If you install the system for a customer, you should follow these rules: • make a drawing of intended location of the items, keeping in mind proper protection for the intended area. • if the customer requests reduction of the system (price reasons etc.
16 Control panel specifications: Electrical Power Backup battery Backup power output 230 VAC, max 0.1 A, supervised, class II 12 V, 1.3 or 2.6 Ah, normal life time 5 years 13VDC, the max. permanent current is 0.4 or 1A for max.