Data Sheet
1 SI CANopen
https://www.ixxat.com/products/products-industrial/canopen-plc-extensions/1-si-canopen-module
1/3
CONFIGURATION
CANOPEN CONFIGURATION AND TIA PORTAL INTEGRATION
Easy integration into the SIMATIC world is one of the most essential requirements when extending of the SIMATIC automation system with networked fieldbus equipment that is not
based on either PROFIBUS or PROFINET. HMS has addressed this need enabling a seamless integration of the 1 SI CANopen module into either SIATIC STEP 7 or TIA Portal.
Configuration of the connected CANopen network is intuitively performed with the optional Anybus Configuration Manager - CANopen.
Once the configuration is finalized, the CANopen network configuration may be uploaded to and stored in the PROFIBUS or PROFINET PLC or the ET200S I/O system CPU. If a 1 SI
CANopen module has to be replaced, the previously stored configuration can be downloaded from the PLC to the new module, significantly reducing down-times in high availability
applications. 1 SI CANopen modules may be replaced while the ET200S is powered.
TECHNICAL SPECIFICATIONS
1 SI CANopen
Plug-in CANopen Master/Slave module for
SIMATIC® ET200S modular I/O system
The 1 SI CANopen module brings CANopen connectivity to the SIMATIC ET200S modular I/O system, enabling full integration
between devices on a CANopen network and the ET200S. Furthermore, the addition of 1 SI CANopen module into the ET200S
system allows a CANopen network to be seamlessly controlled from PROFIBUS and PROFINET.
With the 1 SI CANopen module HMS integrates its CANopen master technology with the SIMATIC architecture. The 1SI CANopen
module enables easy integration of SIMATIC equipment into business segments where CANopen and other CAN based protocols
are used today, also opening up the possibility for PROFIBUS or PROFINET controllers such as the S7 series of advanced
controller devices to interact with CAN and CANopen fieldbus devices (gateways).
The 1 SI CANopen module is supported by all interface and CPU modules of the SIMATIC ET200S modular I/O sytem, with the
exception of the Basic and Compact versions.
HIGHLIGHTS
Plug-in CANopen master/slave module for the SIMATIC ET200S modular I/O system
Connects up to 126 CANopen slave nodes in master mode
SIMATIC ET200S stand-alone operation supported
Module hot swap supported - replacement without removing power
Isochronous mode supported
Pre-build function blocks available for easy PLC programming in SIMATIC STEP 7 or TIA Portal
Can be imported into the hardware catalogue of SIMATIC STEP 7 or TIA Portal
Support for transparent CAN 2.0A protocols
Anybus Configuration Manager CANopen available as part of 1 SI CANopen Startup Kit
Power supply +24 VDC +20 / -15%, supplied from Power module PM-E
Current consumption Max 0.8 W – 33 mA at 24 V
Dimensions Width: 15 mm; Height: 81 mm; Depth: 52 mm