Installation Guide

Table Of Contents
Figure 80PuTTY Screen - Confirm CAM Slot Location
Important! The CAM3S/CAM3M only fits into Slot 5 of the CGR. In this example, the
existing CAM is located in Slot 4. If your existing CAM is located in Slot 5, the same
procedure applies.
11. Type conf t (configuration terminal). The prompt changes to (config), see item 1.
12. Type hw power 4. The CAM in Slot 4 in this example, see item 2.
13. Type do show module, see item 3.
14. If successful, the Status indicates powered-dn (powered down), see item 4.
Note: If powered down is not showing, verify the (config) shows in the prompt. If not, re-
enter conf t. Once (config) shows in the prompt, issue the hw power 4 commend a second
time. Verify that the Status is powered-dn with another do show module command.
02 March 2020 815-0080-00 Itron, Inc. Page 77 of 102
OpenWay® Riva CAM3S and CAM3M Installation Guide 7 Replacing an Existing CAM with a New CAM3S/CAM3M in the Field