Installation Guide

Table Of Contents
Calendar Life
The design calendar (or float) life of the battery extends from eight to ten years at room
temperature (25°C/77°F) under proper charging conditions.
This design life was confirmed by the use of accelerated testing methods that are widely
accepted by both manufacturers and users of sealed-lead batteries. High temperatures are used
to accelerate the aging process of the battery under test.
The float life of a cell is cut in half for roughly every 8°C (14.4°F) rise in ambient temperature. The
example below shows the relationship between ambient temperature and float life for batteries
that have a float life of ten years at 25°C (77°F).
A ten year battery lasts for five years at 33°C (91.4°F) and only years at 41°C (105.8°F).
Preventative Maintenance
Itron recommends a preventative maintenance cycle of a two-year replacement in extreme
environments (average temperatures greater than 110°F/44°C), or five years in non- extreme
environments (average temperatures less than 90°F/31°C).
Replacing the Integrated Battery
The following procedure describes the integrated battery replacement after the equipment is
installed in the field.
CCU100 and Repeater100 Installation Guide 5 Battery Care and Maintenance
12 February 2021 815-0491-00 Itron, Inc. Page 72 of 133