User's Manual

Installation
14 CENTRON® OpenWay™ Meter Technical Reference Guide
The module must be aligned properly in the snaps to avoid damaging
the connector or circuit board.
7 Replace the board-to-board connector by aligning the top of the connector with the
notches in the circuit board and pressing gently at the bottom of connector to mate the
connector to metrology board. Then, gently press the top of the connector to mate it to
the register module. The connector is seated correctly when you hear it snap into place.
Be sure to use the meter base for leverage instead of the LCD holder.
Pressure on the LCD holder may damage the personality module.
8 Ensure the board-to-board connector is fully seated by pressing firmly in on the middle
of the connector.
9 Carefully replace the inner protective cover. Engage the top snaps first, taking care to
place the slot at the top of the cover over the IR light pipe. Failure to do so could break
the light pipe. Ensure that all four meter base tabs are engaged with the slots at the top
and bottom of the inner cover.
10 Place the cover over the meter base until the flange on the cover is flush with the flange
on the meter base.
11 Turn the cover clockwise until the locking tabs are fully engaged with the meter base.