User's Manual

Operation: CVSO OpenWay Register
CENTRON® OpenWay™ Meter Technical Reference Guide 65
Non-Fatal Errors
Error Code Error Possible Cause(s) Error Description
Err ----5-
Clock/
Load
Profile
Error
Load Profile
halted due to
power down with
dead or missing
battery.
This is tested upon power-up.
A set clock with a good battery
present will clear this error. Be
sure to read the Load Profile
data prior to setting the clock
to clear the error. The dead
battery will cause some invalid
intervals at the end of the data.
When the error is cleared,
Load Profile will be restarted
from the beginning to purge
the bad data.
Err -----6
Full
Scale
Overflow
Error
The calculated W
delivered demand
at an EOI
exceeded the
configured full
scale value.
This is tested at a demand
EOI. The maximum demand
register continues to
accumulate and W delivered is
still correctly displayed. When
a demand reset is performed,
the correct maximum W
delivered will be added to the
cumulative register.
A Demand Reset will clear this
error.
If a full scale overflow occurs,
check the installation to ensure
that the current capacity of the
meter has not been exceeded.
A full scale overflow error in no
way affects the existing billing
data.
Err - 9---
SiteScan
Error
SiteScan auto
service detection
could not
determine the
meter’s service
type.
This is tested after the power-
up delay time has expired
following a power-up, an exit
Test mode and a reconfigure
of SiteScan configuration data.
While this condition is present,
SiteScan Diagnostics and
Voltage Quality are disabled.
Once a SiteScan error occurs,
SiteScan will continue to test
for it every 5 seconds until the
service is determined. When
the service is determined, the
error condition is cleared.