5. To view an Item configuration, select Display > Items by Number.
6. Verify that the Honeywell instrument settings are correct. For example, Item number 56 must be set
to 2.0. If the setting is incorrect, click the Change button.
A Change Item pop-up provides the interface to
change the setting.
7. Enter the correct setting. Click Save.
8. Confirm that all settings match the settings required for the ERT module connected to the Honey-
well Instrument. For more information, see compatible ERT modules listed in Honeywell Instrument
500G Installation on page54.
Programming the Honeywell Instrument Parameters
Program the Honeywell Instrument parameters following these Item Code Settings.
Channel A
Corrected
Volume
Channel B
UncorrectedVolume
Channel C Pulse Output Spacing
Instrunment- Pulse
Output
Options
#56 #93 #57 #94 #58 #95 #115 #1014 #1015 Terminal
Board Con-
nections / Wir-
ing
Wiring
ECAT
Pulse
Board
2
Cor
Vol
2
Unc
Vol
2
Cor
Vol
1=1.0sec
Red ERT wire
goes to K
25 July 2019 TDC-1678-005 64
500GERT®Module Installation Guide, RemoteMount Chapter 5 Specific Meter Manufacturer Installation