3d. Confirm that the meter was added to the Phone Book.
3e. Set up the corrected or uncorrected parameters.
3f. From the Talk to Unit tab, select Setup > Default.
3g. Set the following Default Setup Group parameters:
Enter the desired Cor. Volume Unit parameter. Set
Cor. Pulse Volume to the same number of units.
For Output Pulse Spacing, enter the largest number
over 285mS that works for your application. Itron
recommends a setting of 350mS.
For Output Pulse Width, enter the largest number
over 28mS that works for your application. Itron
recommends a setting of 30mS.
3h. Click Send at the bottom of the page.
3i. Select Current Page.
ECM2 programming
4. Set the ECM2 output pulse spacing to 750ms for operation with the 500G remote module. Output spacing
represents an off-time between pulses.
Sensus Meter Installation
This section describes remote module installation on compatible Sensus meters.
Cellular 500G Module Remote Installation Guide 5 Specific Meter Manufacturer Installation