Installation Guide

Table Of Contents
Galvanic Mechanical and Wiring Installation Instructions
GAS Micro wiring connections
GAS Micro corrector P13 connection 100G module wires
Pulse output1-C C1 Blue/white
Pulse output1-E C2 Red
Pulse output2-E C3
Pulse output2-C C4
Programming the Galvanic Gas Micro Electronic Volume Corrector
For more information about programming the Galvanic Gas Micro Electronic volume corrector,
see the GAS MICRO Operator's Manual, Galvanic part number MA1956. Contact Galvanic
Applied Sciences, Inc to obtain the operator's manual.
GE Oil and Gas Meter Installation
This section provides the instructions to install the remote module on the following compatible
GE Oil and Gas meters.
Meter model Meter notes Itron part
number
module notes
D800/D1000
Pulse width must be
set greater than 100
ms. Firmware version
must be 1.71 or
higher.
ERG-7000-
503
ERG-7000-
505
Both modules
are compatible
with these meter
models.
B3 Series pulse output meter
LMMA pulse output meter
Rotary meters
equipped with
WeighandWire solid
state pulsers. Meter
must have factory-
installed pulser with
connector output.
Purchase correct
cable interface from
GE Dresser. Pulser
must be version 17 or
higher.
ERG-7000-
503
Cellular 500G Module Remote Installation Guide 5 Specific Meter Manufacturer Installation
10 March 2021 815-0622-00 REV 000 Itron, Inc. Page 41 of 91