Installation Guide

Register Error Flag
The Register Error flag sets if the Register Error Detected flag is active for 24 hours.
The Register Error Flag remains active for 40 days in Mobile Mode.
Register Error Detected
Register Error Detected indicates that the Cellular 500W Pit Module is not communicating
with the register/meter. The event or alarm flag automatically clears after the Cellular
500W Pit Module receives a successful read from the register.
Note: The Register Error Detected flag may be an indicator of a damaged register.
Low Battery Warning
The low battery warning allows the utility to easily identify which water modules are
nearing end-of-life in a mixed population and gives the utility the opportunity to schedule
replacement.
The pit modules include a battery life estimator. The estimator is based on the number of
data packets sent at the various power levels and the age (self-discharge) of the Cellular
500W Pit Module.
Note: The low battery warning is a single flag that is set when the battery has less than
10% remaining capacity, which typically corresponds to 2 years of battery life
remaining. Battery life is evaluated daily at midnight.
Network Mode
The Cellular 500W Pit Module reports the tampers available in Mobile Mode and extended
meter alarms available from solid-state and electronic meters connected to the Cellular 500W
Pit Module. The extended alarms include:
Empty pipe
Temperature
High flow
Meter low battery
Meter tampering
Reverse flow
Zero consumption
Firmware Functionality
This section lists the Cellular 500W Pit Module firmware information and lists functionality by
version.
Cellular 500W Module Pit Installation Guide 1 Introduction
October 13, 2021 815-0617-00 REV000 Itron, Inc. Page 11 of 40