User's Manual Part 2

Electronic Instrument Installation
TDC-0838-001 2.4GZ OpenWay Gas Module Installation Guide - Remote Mount 55
Proprietary and Confidential
To test the 2.4GZ OpenWay remote mount gas module IMC\W2 installation
1. Connect the IMC\W2 to the PC using the serial cable.
2. Using the Dresser ROOTS
®
User Terminal (UT) communications software, connect to the IMC\W2.
3. Read the uncorrected or corrected count number on the 2.4GZ OpenWay remote mount gas module with
the Itron endpoint reading device. Compare the IMC\W2 uncorrected or corrected amounts to the 2.4GZ
OpenWay remote mount gas module.
4. Input approximately 20 pulses to the 2.4GZ OpenWay remote mount gas module. Verify the uncorrected
or corrected counts on the IMC\W2 and the 2.4GZ OpenWay remote mount gas module are the same.
Programming the 2.4GZ OpenWay Remote Mount Gas Module
Assembly
Caution The 2.4GZ Remote Mount Gas Module must be programmed before use.
Program the 2.4GZ OpenWay remote mount gas module with a Bluetooth-enabled FC200 or FC300 with
SRead handheld computer and ZigBee Belt Clip Radio loaded with Endpoint-Link
or Endpoint-Link Pro
software version 5.3.1.26 or version 5.5 for Itron Private Profile (IPP) gas modules (OWG-5001-XXX).
Endpoint-Link Pro software version 5.5 must be used for Smart Energy Profile (SEP) gas modules
(OWG-5002-XXX). See the Endpoint-Link Endpoint Programming Guide (TDC-0744) for more
complete programming information. An Itron magnet is also required for programming.
FC200SR FC300 with SRead Zigbee Belt Clip Radio Itron Magnet