User's Manual Part 2

Diaphragm Meter Installation
TDC-0838-001 2.4GZ OpenWay Gas Module Installation Guide - Remote Mount 62
Proprietary and Confidential
Note If the reading is not higher than the previous reading, the 2.4GZ OpenWay remote mount gas
module is not reading. Repeat steps 3, 4, and 5. If the 2.4GZ OpenWay remote mount gas module is still
not counting, replace the 2.4GZ OpenWay remote mount gas module and perform steps 3, 4, and 5.
6. Align the large notch in the side of the magnet hub spacer with the needle of the meter drive rate dial (1
foot or 2 foot for residential diaphragm meters; 5, 10, or 100-foot for commercial diaphragm meters).
7. Press the magnet hub spacer down over the dial needle as far as possible. The tip on the bottom of the
spacer may touch index face. Turn the dial after hub spacer installation to verify the index dial functions
with a smooth, easy rotation.
8. Align the pointer (1) on the top of the magnet hub and the notch (2) in the side of the magnet hub with the
needle (3) of the meter drive rate dial.