User's Manual Part 1
Electronic Instrument Installation
TDC-0838-001 2.4GZ OpenWay Gas Module Installation Guide - Remote Mount 39
Proprietary and Confidential
Mercury corrector programming parameters:
Caution A Mercury Instrument Volume Correctors must have a Form A board. A Form C board
is not compatible with the 2.4GZ OpenWay remote mount gas module.
For TCI, when using both outputs, items 1014 and 1015 must be set to Itron.
Item #056: Pulse A Scaling. Set at 2.0000 for a form A switch.
Item #057: Pulse A Scaling. Set at 2.0000 for a form A switch.
Item #058: Pulse A Scaling. Set at 2.0000 for a form A switch.
Item #090: Corrected Volume Units: Code (0-20) selects the unit of measure for Corrected Volume
(Item000) and other "CorrVol" related items.
Item #092: Uncorrected Volume Units: Code (0-20) selects the unit of measure for Uncorrected Volume
(Item002) and other "UncVol" related items.
Item # 093, 094, 095: Type of gas volume information to be sent. For "CorrVol" selected, must be set at 0.
Item # 096: Corrected Volume Display: Must be set at 1, 2, 3 or 4 blanks. Endpoint does not support a
setting of 0 blanks.
Item # 097: Uncorrected Volume Display: Must be set at 1, 2, 3, or 4 blanks. Endpoint does not support a
setting of blanks.
Item # 098: Check drive rate of the corrector. Should be the same as the plate above the uncorrected dials
and the same as the plate on the index drive of the meter.
Item # 115: Output Pulse Code: Must be set at 1 or 2.