Pipe Preparation
TDC-0909-000 100W Datalogging Endpoint Installation Guide 25
Proprietary and Confidential
4. Insert the mounting plate over the U-bolt's threaded screw ends. Attach the two wing
nuts over the clamp screw ends and tighten the wing nuts until snug (to a minimum of
5-inch pounds) to prevent device rotation on the pipe. After the second wing nut is
tightened, check the Leak Sensor to verify the device is snug. If the sensor moves,
tighten the wing nuts until there is no movement.
Caution Do not tighten the Leak Sensor to more than 20 inch-pounds. Over-
tightening could damage the Leak Sensor housing and/or the pipe.
Note Leak Sensor mounting orientation is not critical. Orient the Sensor to best
accommodate your installation. The most important installation practice is to mount
the Sensor securely to the pipe.