User's Manual

Chapter 4 Installing the 100W Datalogging Endpoint
24 TDC-0909-000 100W Datalogging Endpoint Installation Guide
Proprietary and Confidential
To install the Leak Sensor on a pipe or meter insetter
1. Select a Leak Sensor mounting location within 5 feet of the 100W endpoint. Mount
the sensor on the water input side of the meter.
Caution The Leak Sensor must be mounted on the water input side of the meter.
Failure to follow this mounting requirement could result in errors in the leak detection
data. Installation requires Itron mounting hardware. Repair costs and service charges
relating to the use on non-compliant mounting hardware will be charged to the
customer. Contract Itron Support for more information.
2. Verify the pipe’s mounting surface is free from dirt and debris. Place the curved
surface of the LS against the pipe.
3. Insert the mounting U-bolt over the pipe and into the LS mounting holes.
Caution Do not mount the Leak Sensor on a pipe coupler, joint, or nut.