User's Manual

Chapter 4 Installing the 100W Datalogging Endpoint
20 TDC-0909-000 100W Datalogging Endpoint Installation Guide
Proprietary and Confidential
Optional Leak Sensor Installation
Leak Sensors analyze water flow sound patterns to detect new, evolving, and pre-existing
leaks. LS analysis data is uploaded to mlogonlineā„¢ Network Leak Monitoring for data
analysis accessed through a secure Internet portal unique to your utility.
The 100W endpoint stores 20 days of Leak Sensor data. On the 21
st
day, the 100W begins to
write over stored data in a first in, first out manner, maintaining current data on the status of
the surrounding water pipes.
The 100W automatically detects the presence of connected Leak Sensors. The 100W will
automatically detect the Leak Sensor within 22.5 minutes and begin reading leak sensor
data. To immediately detect the Leak Sensor and begin reading data, perform a Check ERT
with a handheld computer running FDM software.
This section describes installation of the Leak Sensor (LS) in a 100W system. The LS is
used in both indoor (basement) and outdoor (water meter pit) locations. LS devices are
mounted on a water service pipe or meter insetter (meter horn) and connect to the blue, top
connector of the 100W endpoint. The mounting bracket shipped with the Leak Sensor
accommodates an (up to) 1 1/2-inch OD pipe. An optional mounting bracket is available for
pipe sizes (up to 2 1/2-inch OD.
Required Equipment
Equipment
Itron Part Number
Description
Leak Sensor
LDS-0001-002
LDS with inline connector, environmental
connector cap; 5-foot cable, and mounting bolt
(fits up to 1 1/2-inch OD pipe).
Optional mounting bracket
CFG-0349-002
Mounting bolt fits up to 2 1/2-inch OD pipe.
100W datalogging endpoint
ERW-1300-002
Dual port 100W for LS and environmental
connector caps.
25-foot extension cable
CFG-0349-101
25-foot cable with coordinating connectors (LS
blue connector, register black connector).
100W LS environmental
replacement cap
MSC-0019-005
Protects Leak Sensor connector when the Leak
Sensor is not connected to the 100W endpoint.
Leak Sensor Mounting bracket 100W endpoint Optional mounting bracket
Warning When the 100W is installed but the Leak Sensor is not attached,
the blue Leak Sensor port must be protected with the environmental cap
(MSC-0019-005).If the Leak Sensor is removed from the 100W, the
environmental cap must be replaced to protect the connector.