-1346-000 100T-HON Honeywell Telemetry Module Installation Guide 26
Proprietary and Confidential
After the 100T-HON telemetry module is installed, you must program the module using an Itron handheld or
900MHz Belt Clip Radio and your PC loaded with Field Deployment Manager (FDM) software. FDM
supports configuration of the following parameters:
(Optional) Injecting ChoiceConnect security keys.
Setting the fixed network or mobile operation mode (setting the operation mode establishes the transmit
power, default packet type, and BUP rates).
Setting the Honeywell communication access code.
Setting the utility ID.
Setting the 100T-HON telemetry module time.
Setting connected device-specific parameters:
Honeywell EVC devices
o Configure channel 2 (for none, electronic uncorrected volume, or mechanical uncorrected
volume).
o For mechanical uncorrected volume channel 2 only (implies the existence of an uncorrected
mechanical input):
initial index read
drive rate
Configure gas day take (GDT) options.
Enable or disable GDT
GDT capture time
GDT BUP frequency
Number of GDT transmissions
Caution You must program the 100T-HON telemetry module before use.
C HAPTER 4
Programming the 100T
-HON Telemetry Module