User's Manual
Electronic Instrument Installation
Programming the Honeywell Instrument Parameters
Item Code Settings
Channel A
Corrected
Volume
Channel B
Uncorrected
Volume
Channel C Pulse Output Spacing
Instrument Pulse Output Options #56 #93 #57 #94 #58 #95 #115 #1014 #1015 Terminal Board Connections/Wiring
ECAT
Pulse Board Ver-2(3)
Form-A
2 Cor Vol 2 Unc Vol 2
Cor
Vol
1 = 1.0 sec
2 = 2.0 sec
or
4 = 0.5 sec
Red ERT wire goes to K
Blue and White ERT wires go to Y
Connection must be on same terminal board channel
(for example, Ka/Ya; kb/Yb; Kc/Yc)
Ka, Ya = Channel A
Kb, Yb = Channel B
Kc, Yc = Channel C
Pulse Board Ver-3(2)
Form-C1 Form-A
2
Cor
Vol
Mini with
Form A Main
board
Main Board Type-2* 2 Cor Vol
Mini-AT
JB29, JB30 & JB31
Jumpered for Form-A*
2 Cor Vol 2 Unc Vol
Mini-Max All main boards 2 Cor Vol 2 Unc Vol
1 = 1.0 sec
or
2 = 2.0 sec
TCI
Form A main board
2
Cor Vol
2
Cor Vol
Itron
100G
Itron
100G
Channel A
ERT TCI
White Orange and Brown
Red Yellow
Blue Blue (Alarm)
Channel B
ERT TCI
White and Blue White
Red Green
Module does not support Form-C pulse output board.
100G modules do not support 8 digits (0 blank) configurations (Item #96 and Item #97)
*For optional SPA Board, jumper must be installed on J1-B as indicated in the Mercury Quick Reference
Guide (page 148) for Form A.
IItem #90 is used to set unit of measure for corrected volume.
Item #92 is used to set unit of measure for uncorrected volume.
Item #98 is used to set drive rate for the corrector. Should be the same as the plate above the uncorrected dials
and the same as the plate on the index drive of the meter.
TDC-0824-014 100G Series Gas ERT Module Installation Guide, Remote Mount 43