User's Manual

Electronic Volume Corrector and Instrument Installation
TDC-0824-003 100G Datalogging FN ERT Module Installation Guide - Remote Mount 40
Proprietary and Confidential
15. Connect the uncorrected module wires to the Input Switch Board UNC. VOL following the table below.
Uncorrected ERT Module Connections
ERT Module
Mini-Max Input
Switch Board UNC. Vol.
Red wire
COM terminal
Blue wire*
NO terminal
White wire*
NO terminal
*Twist the blue and white ERT module wires together before connecting to the Mini-Max board.
Tighten terminal connections securely.
16. Tighten the large strain relief securely.
Warning Do not crush the endpoint through-cables when tightening the strain relief.
17. Re-install or reconnect the power or battery sources.
18. Close the instrument case and tighten the case screw securely. Replace any locks that were removed for
installation.
Wiring the Remote ERT Module to the Mercury TCI
The Mercury Instruments Temperature Compensating Index (TCI) provides two Form-A volume pulse
outputs and one Form-B alarm output. These outputs are electronic switches. The first two pulse outputs are
configurable for compensated or uncompensated volume. The third output (Form-B) is for alarm output use
only.