User's Manual

Electronic Volume Corrector and Instrument Installation
TDC-0824-003 100G Datalogging FN ERT Module Installation Guide - Remote Mount 35
Proprietary and Confidential
Programming the Mercury Instrument
Code Settings
Volume
Instrument
Type
Item Code Settings and Corresponding Terminal Board Channel
Terminal Board Connections*
Pulse Output
Options
Channel A
Channel B
Channel C
Number of
Blanked digits
on CorVol
Display
Pulse Output Spacing
Ka, Ya = Channel A
#056
#93
#057
#094
#058
#095
#96
#115
#1014
#1015
ECAT
Pulse Board Ver-1(3)
Form-C
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Module does not support a Form-C pulse output
board.
Pulse Board Ver-2(3)
Form-A
2.0000
0
2.0000
0
2.0000
0
1, 2, 3, or 4
1, 2, 3, or 4
n/a
n/a
Ka, Kb, Kc (Red Wire)
Ya, Yb, Yc (Blue & White Wire)
Connection must be on same terminal board
channel (for example, Ka/Ya; Kb/Yb; Kc/Yc).
Pulse Board Ver-3(2)
Form-C1 Form-A
n/a
n/a
n/a
n/a
2.0000
0
1, 2, 3, or 4
1, 2, 3, or 4
n/a
n/a
Kc (Red Wire) Y (Blue & White Wire). For this
option, module must be connected to Channel C.
Mini with
Form A
Mainboard
Main Board Type-2
2.0000
0
n/a
n/a
n/a
n/a
1, 2, 3, or 4
1, 2, 3, or 4
n/a
n/a
K (Red Wire) Y (Blue & White Wire).
For optional SPA Bd., jumper must be installed
on J1-B as indicated in the Mercury Quick
Reference Guide (page 148) for Form A.
Mini-AT
JB29, JB30 & JB31
Jumpered for Form-
A
2.0000
0
2.0000
0
n/a
n/a
1, 2, 3, or 4
1, 2, 3, or 4
n/a
n/a
K (Red Wire) Y (Blue & White Wire).
For optional SPA Bd., jumper must be installed
on J1-B as indicated in the Mercury Quick
Reference Guide (page 148) for Form-A.
JB29, JB30 & JB31
Jumpered for Form-
C
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Module does not support a Form-C pulse output
board.
Mini-Max
All Main Boards
2
0
2
0
n/a
n/a
1, 2, 3, or 4
1, 2, or 4
n/a
n/a
K (Red Wire) Ya or Yb (Blue & White Wire)
TCI
Form C Main Board
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Module does not support a Form-C pulse output
board.
Form A Main Board
2.0000
0
2.0000
0
n/a
n/a
1, 2, 3, or 4 blanks
(7, 6, 5, or 4 active)
n/a
Itron selection
in dropdown
menu.
Itron selection
in dropdown
menu
Connections to channels of output pulses are
made through loose unterminated cable wires
and gel connect connectors.
Notes:
Code 0 for items 093, 094 & 095 = Corrected Volume Pulse Data
Code 1 for item 115 = 1.000 Sec.
Code 2 for item 115 = 2.000 Sec.
Code 1 for item 096 = blank 1 digit and display 7 digits
Code 2 for item 096 = blank 2 digits and display 6 digits
Code 3 for item 096 = blank 3 digits and display 5 digits
Code 4 for item 096 = blank 4 digits and display 4 digits
*For more information, see pages 11-20 of the "Basic Pulse Information for Mercury Instruments, Inc., Electronic Volume Correctors" manual, or contact Mercury Instruments at
513-272-1111.