User's Manual
Mounting the 100G Datalogging FN Remote ERT Module
TDC-0824-003 100G Datalogging FN ERT Module Installation Guide - Remote Mount 7
Proprietary and Confidential
Mounting Installation Considerations
Select a proper mounting location. Itron recommends mounting the 100G Datalogging FN remote ERT
module in close proximity to the meter or instrument. Some applications may require an extended cable-
length. The 100G Datalogging FN remote ERT module supports cable lengths up to 300 feet.
Mount the 100G Datalogging FN remote ERT module in a vertical position with the ERT module label
directional arrow pointed upward.
Caution Upright vertical positioning is very important because:
100G Datalogging FN remote gas modules are designed with the antenna in a
vertical direction so the antenna is parallel to the reading device (which has a
vertical antenna). Matching antenna polarity can greatly affect RF performance
and enable easy ERT module reading.
100G Datalogging FN remote gas modules are designed so the tilt tamper is
vertical. It is important to maintain vertical positioning in the field to enable tilt
tamper stability.
Warning Do not mount the 100G Datalogging FN remote ERT module in an orientation other
than vertical (remote ERT module label arrow pointed upward or downward). Violating the
mounting orientation requirements will void the product warranty.