User's Manual
TDC-0823-005 100G Datalogging Installation Guide - Direct Mount 83
Proprietary and Confidential
To program the 100G Datalogging gas endpoint
1. Program the meter drive rate into the 100G Datalogging gas endpoint using the endpoint programming
device. For all programming and "Check Endpoint" operations, hold the handheld computer as close to
vertical as possible. For best success, keep the handheld computer within 6 feet of the target endpoint.
Verify you have the correct programming mode (Fixed Network Mode, Mobile/Handheld Mode, or Hard
to Read Mobile/Handheld Mode) for your application. Programming parameters are based on the
configuration file loaded into the endpoint programming device.
During programming, the 100G Datalogging gas endpoint is set to the nearest 100 cubic feet; the last two
digits (tens and units) are programmed as zeros (0). After programming is complete, the endpoint
assembly will read to the nearest cubic foot.
2. Slowly turn the endpoint's drive wriggler two turns in the direction shown on the index drive rate. This
verifies the endpoint is counting properly after assembly.
Caution Do not turn the drive wriggler faster than one turn per second.
3. Read or Check the 100G Datalogging gas endpoint using the endpoint programming device.
If the read result is higher than the number programmed in Step 1, the 100G Datalogging gas endpoint
is counting correctly.
If the read result is not higher than the number programmed in Step 1, replace the 100G Datalogging
gas endpoint.
B3, LMMA, and S3A CTR/TC Dresser ROOTS® Series Register
Settings and Direct Drive Programming Information
Use the information in the following tables to program Dresser ROOTS
®
Series B3, LMMA, and S3A Non-
compensated Counter (CTR) and Temperature Compensated (TC) registers. Reference the Meter
Compatibility List to confirm compatibility.
Settings for Series B3 Registers
Settings for LMMA Registers
Model
Meter size
Settings
Model
Meter Size
Settings
CTR
8C-15C and 2M-11M
16M-56M
Number of dials: 5
Drive rate: 10
PCOMP factor: NONE
Number of dials: 6
Drive rate: 100
PCOMP factor: NONE
CTR
1.5M-11M
16M
Number of dials: 5
Drive rate: 10
PCOMP factor: NONE
Number of dials: 6
Drive rate: 100
PCOMP factor: NONE