User's Manual

Sensus/Rockwell Meter Installation
TDC-0823-005 100G Datalogging Installation Guide - Direct Mount 26
Proprietary and Confidential
Install the remaining three mounting screws and tighten in the pattern shown in the photo.
a. Insert lower left mounting screw and tighten to snug position.
b. Tighten upper right mounting screw to snug position.
c. Insert upper left mounting screw and tighten to snug position.
d. Insert lower right mounting screw and tighten to snug position.
Tighten each mounting screw evenly.
Important Meter manufacturers: torque the mounting screws 15 to 20 inch-pounds.
3. Place a new tamper seal over the two screws with tamper seal cups. Press the new tamper seals into place
using an 11/32-inch nut driver (or similar blunt tool).
4. Complete any necessary paperwork and properly dispose excess installation materials and scrap from the
customer premises.