5. Environmental Requirements
5.1 Temperature
Operating Ambient, normal mode (inlet air): 0°C ~ 4 C (32°F~ 11F)
Non-operating Ambient:: -40°C ~ 70°C (-40°F~ 158°F)
5.2 Humidity
Operating: 20% ~ 90%RH non-condensing
Non-Operating: 5% ~ 95%RH non-condensing
5.3 Altitude
Operating: Sea level to 10,000 ft
Non Operating: Sea level to 40,000 ft
5.4 Mechanical Shock
Non-Operating: 50 G Trapezoidal Wave, 11mS half sin wave. The shock is to be applied in each of the
orthogonal axes.
5.5 Vibration (Non-Operating)
The power supply shall be subjected to a vibration test consisting of a 10 to 300 Hz sweep at a constant
acceleration of 2.0g for duration of one (1) hour for each of the perpendicular axes X, Y and Z (0.1
octave/minute). The output voltages shall remain within specification.
5.6 Electromagnetic Compatibility
Table 12 EMC Requirements
Electromagn
etic
Interference
FCC CFR Title 47
Part 15
Sub Part B
EN55022/EN55024
Conducted B Class
Radiated B Class
Harmonics IEC61000-3-2 Class D
Flicker IEC61000-3-3
ESD
Susceptibility
EN-61000-4-2
8KV by Air, 4KV by Contact
Performance Criteria B
Radiated
Susceptibility
EN61000-4-3
80MHz~1000MHz
(3V/m(mns) Amplitude 80% AM 1KHz
Criteria A
EFT/Burst EN61000-4-4 5KHz, AC: 1KV, DC: 0,5 KV, Performance Criteria B
Surge
Voltage
EN61000-4-5
Line-to-Line: 1KV
Line-to-Ground: 2KV
Performance Criteria B
Conducted
Susceptibility
EN61000-4-6
0.15MHz~80MHz
3V/m Amplitude 80% AM 1KHz
Performance Criteria A
RF EN61000-4-8 50 Hz/3A(ms)/m Performance Criteria A