Instruction Manual
iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) - Italy |
support@ismacontrolli.com
www.ismacontrolli.com Installation Instruction| 1
st
Issue rev. 3 | 01/2022 page 2
Registered access
Modbus
Dec
Hex
Register Name
Access
Description
30001
0
0x00
Version/Type
Read
Version and Type of the
30002
1
0x01
Switches
Read
Switches state
40003
2
0x02
Baud rate
Read & write
RS485 baud rate
40004
3
0x03
Stop Bits & Data Bits
Read & write
No of Stop bits & Data Bits
40005
4
0x04
Parity
Read & write
Parity bit
40006
5
0x05
Response Delay
Read & write
Response delay in ms
40007
6
0x06
Modbus Mode
Read & write
Modbus Mode (ASCII or RTU)
40009
8
0x08
Watchdog
Read & write
Watchdog
40013
12
0x0C
Default Output State
Read & write
Default output state (after
40018
17
0x11
Inputs filter
Read & write
Configuration of the inputs
40033
32
0x20
Received packets LSR
(Least Significant Reg.)
Read & write
No of received packets
40034
33
0x21
Received packets MSR
(Most Significant Reg.)
Read & write
40035
34
0x22
Incorrect packets LSR
Read & write
No of received packets with
error
40036
35
0x23
Incorrect packets MSR
Read & write
40037
36
0x24
Sent packets LSR
Read & write
No of sent packets
40038
37
0x25
Sent packets MSR
Read & write
30051
50
0x32
Inputs
Read
Inputs state
40052
51
0x33
Outputs
Read & write
Output state
40053
52
0x34
Counter 1 LSR
Read & write
32-bit counter 1
40054
53
0x35
Counter 1 MSR
Read & write
Modbus
Dec
Hex
Register Name
Access
Description
40055
54
0x36
Counter 2 LSR
Read & write
32-bit counter 2
40056
55
0x37
Counter 2 MSR
Read & write
40057
56
0x38
Counter 3 LSR
Read & write
32-bit counter 3
40058
57
0x39
Counter 3 MSR
Read & write
40059
58
0x3A
Counter 4 LSR
Read & write
32-bit counter 4
40060
59
0x3B
Counter 4 MSR
Read & write
40061
60
0x3C
Counter 5 LSR
Read & write
32-bit counter 5
40062
61
0x3D
Counter 5 MSR
Read & write
40063
62
0x3E
Counter 6 LSR
Read & write
32-bit counter 6
40064
63
0x3F
Counter 6 MSR
Read & write
40065
64
0x40
Counter 7 LSR
Read & write
32-bit counter 7
40066
65
0x41
Counter 7 MSR
Read & write
40067
66
0x42
Counter 8 LSR
Read & write
32-bit counter 8
40068
67
0x43
Counter 8 MSR
Read & write
40085
84
0x54
CCounter 1 LSR
Read & write
32-bit value of captured
counter 1
40086
85
0x55
CCounter 1 MSR
Read & write
40087
86
0x56
CCounter 2 LSR
Read & write
32-bit value of captured
counter 2
40088
87
0x57
CCounter 2 MSR
Read & write
40089
88
0x58
CCounter 3 LSR
Read & write
32-bit value of captured
counter 3
40090
89
0x59
CCounter 3 MSR
Read & write
40091
90
0x5A
CCounter 4 LSR
Read & write
32-bit value of captured
counter 4
40092
91
0x5B
CCounter 4 MSR
Read & write
Modbus
Dec
Hex
Register Name
Access
Description
40093
92
0x5C
CCounter 5 LSR
Read & write
32-bit value of captured
counter 5
40094
93
0x5D
CCounter 5 MSR
Read & write
40095
94
0x5E
CCounter 6 LSR
Read & write
32-bit value of captured
counter 6
40096
95
0x5F
CCounter 6 MSR
Read & write
40097
96
0x60
CCounter 7 LSR
Read & write
32-bit value of captured
counter 7
40098
97
0x61
CCounter 7 MSR
Read & write
40099
98
0x62
CCounter 8 LSR
Read & write
32-bit value of captured
counter 8
40100
99
0x63
CCounter 8 MSR
Read & write
40117
116
0x74
Counter Config 1
Read & write
Counter Configuration
+1 – time measurement (if 0
counting impulses)
+2 – autocatch counter every
1 sec
+4 – catch value when input
low
+8 – reset counter after catch
+16 – reset counter if input
low
+32 – encoder (only for
counter 1 and 3)
40118
117
0x75
Counter Config 2
Read & write
40119
118
0x76
Counter Config 3
Read & write
40120
119
0x77
Counter Config 4
Read & write
40121
120
0x78
Counter Config 5
Read & write
40122
121
0x79
Counter Config 6
Read & write
40123
122
0x7A
Counter Config 7
Read & write
40124
123
0x7B
Counter Config 8
Read & write
40133
132
0x84
Catch
Read & write
Catch counter
40134
133
0x85
Status
Read & write
Captured counter