Owners Manual
Table Of Contents
- Introduction
- Applications
- Product Overview
- Chassis Features and Benefits
- Ordering Data - EZ Series 42
- Performance Data - EZ Series 42
- Ordering Data - EZ Series DR (DR.PTAC)
- Performance Data - EZ Series DR (DR.PTAC)
- Dr. PTAC Features
- Dr.PTAC information
- Dimensional drawings
- Options and Accessories
- Clearances and Projections
- Installation Instructions
- Wall Sleeve Installation Instructions
- Condensate Drain Kit
- Rear Grille Installation Instructions
- Subbase Assembly & Installation
- Chassis Installation
- Front Cover Installation & Removal
- Fresh Air Vent
- Maintenance
- Information for Heat Pump units
- Electrical Installation
- Wiring Diagram
- System Controls and Management
- Digital Control Panel
- Remote Thermostats
- Remote Thermostat Interface
- Control Board
- Temperature Limiting
- Error Codes
- Performance Specifications
- Warranty
Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
16
Clearances and Projections
MINIMUM PROJECTION INTO ROOM
e wall sleeve will need to be installed so that the sleeve
projects into the room a minimum amount according to
the table below.
OPTION
MINIMUM
PROJECTION
INCHES (MM)
WALL SLEEVE ONLY .25 (6)
SUBBASE KIT
4.5(114)
LEVELING LEGS KIT 2 (50)
DUCT KIT 1.0 (25.4)
MINIMUM CLEARANCE FOR SUBBASE, LEVELING LEGS, AND
LATERAL DUCT KIT
Installation of these kits requires drilling of mounting
holes on both sides of the wall sleeve. e minimum
required clearance distance between the wall sleeve and
oor wall is shown in the rst column of the table below.
e minimum clearance between the wall sleeve and
adjacent (perpendicular) walls is shown in the second
column. If the distance between wall sleeve and adjacent
wall will be at or near the minimum clearance distance,
mount these kits on the sleeve before installing the sleeve
in the wall.
OPTION
MINIMUM CLEARANCES
TO FLOOR WALLS
INCHES INCHES
WALL SLEEVE ONLY 3 0
SUBBASE KIT 3 3.25
LEVELING LEGS 3 3
DUCT KIT 3 0
DRAIN KIT 3 1.5
HARD-WIRE KIT 3 1.25
OUTSIDE WALL ROOM SIDE
1/4”
MINIMUM
WALL
SLEEVE
MINIMUM
ROOM SIDE
PROJECTION
(SEE TABLE)
Figure 2 Minimum Projection Into Room
OUTSIDE WALL ROOM SIDE
1/4”
MINIMUM
WALL
SLEEVE
MINIMUM
ROOM SIDE
PROJECTION
(SEE TABLE)
MINIMUM
CLEARANCE
TO FINISHED
FLOOR
(SEE TABLE)
Figure 3 Minimum Clearance From Floor
OUTSIDE WALL
INTERNAL
ADJACENT
WALL
TOP VIEW
WALL SLEEVE
MINIMUM
CLEARANCE FROM WALL
Figure 4 Minimum Clearance From Walls