JayBox Installation Manual
©
2022 IRONRIDGE, INC. VERSION 1.2 JAYBOX INSTALLATION MANUAL - 3
RATINGS
Product Markings are located on the inside
of the Jaybox Lid.
MARKINGS
UL 1741 LISTED
Photovoltaic Junction Box Conforms to UL STD 1741 and Certied to CSA STD C22.2 No. 107.1
• Maximum System Voltage: 1500 Volts
• Maximum Total Current (Isc): 100 Amps
• Maximum Current Per String (Isc): 30 Amps
• Maximum Number of Input Circuits: 4 - Combined circuits not to exceed 100 Amps
• Ambient Operating Conditions: -35°C to 75°C (-31°F to 167°F)
• Enclosure Rating: Type 3R Rainproof
Allowable Wire Sizing:
• Inputs: 12 AWG - 10 AWG
• Outputs: 12 AWG - 8 AWG
• Ground: 10 AWG - 6 AWG
Roof Specictions:
• Roof Slope Range: 2:12 and above
• Attic Conduit Pass-Through Fitting Size Range: 1/2” - 1 1/4"
• Max Attic Pass-through Conduit Fittings: 2
• Max Side Wall Conduit Fitting Size: 1 1/4"
Interior Dimensions:
• Box: 8" W x 8"D x 3” H
• Box Volume: 150 in3
• Flashing: 12"W x 9"D
Water Seal Ratings:
• UL 441
• TAS 100(A)-95
Approved wire connectors: UL486C or UL486D Listed Wire Connectors for Wire Gauge 12ga to 6ga.
Approved Conduit Fittings: UL514B Listed rain tight or wet location conduit connectors or ttings for entry into the
enclosure.
#5021605