Power voltage
Wireless protocol
Radio frequency
Radio range
Radio Power output
Control channel
Control group
Op. humidity
Op. temperature
Dimensions
120/277VAC, 50/60 Hz
Modified Zigbee Light Link (ZLL)
2405 - 2475MHz
Typical 50 ft. @indoor
Max. 3 dBm
4
1-4 per channel
Max 95% non-condensation
-14°F ~ 122°F (-10°C ~ 50°C)
4.13”H x 1.77”W x 1.65”D (w/mounting plate)
SPECIFICATIONS
To create a new OS-NET network, ensure no other “open”
OS-NET at site. Use the EZ-GROUP function to assign two
“ungrouped” devices with the same group within 1 minute.
NOTE: If the target network already existed and unlocked, skip
this section and start adding the device to the network.
Creating a New OS-NET Network
NOTE: The button will automatically exit Configuration Mode after
a successful grouping. If grouping fails, the LED will blink twice
per second in BLUE and the button will stay in the Configuration
Mode for another 90 seconds. If no configuration conducted
within 90 seconds, the device will exit the Configuration Mode.
To exit Configuration Mode manually, press the LEFT and RIGHT
parts of the channel button and hold for more than 3 seconds.
After installed, each OS-NET Button should be grouped and
linked with the same OS-NET network to enable manual
control of grouped lighting. An “ungrouped” OS-NET Button
is functionless.
NOTE: For the first time configuration, please
learn basic operation of SRP-281 and
understand all about OS-NET configuration
from the OS-NET Programming Guide.
CONFIGURATION OPERATIONS
1. Turn On the light
A SHORT press (≤0.5 second) at the RIGHT part of the
channel button will transmit a command to turn ON the
grouped lighting. Light will stay on as long as any of the
grouped sensor(s) detects occupancy. Grouped sensor(s) will
resume control after the area is vacated.
2. Turn Off the light
A SHORT press (≤0.5 second) at the LEFT part of the channel
button will transmit a command to turn OFF the grouped
lighting. Grouped sensor will resume control after the delay
time elapsed.
3. Ramp up the light
A LONG press (≧0.5 second) and hold at the RIGHT part of
the channel button will enter into dimming mode and ramp up
the grouped lighting output to maximum 100%. Intermittent
press on the button during dimming mode will step up the
output level gradually. The device will exit from dimming mode
2 seconds after the last button operation.
4. Fade down the light
A LONG press (≧0.5 second) and hold at the LEFT part of the
channel button will enter into dimming mode and fade down
the grouped lighting output to 10% and OFF. Intermittent press
on the button during dimming mode will step down the output
level gradually. The device will exit from dimming adjustment
mode 2 seconds after the last button operation.
NOTE: After changing the dim level, allow the LED bar of the
device to exit from dimming mode.
Programming Guide
DEVICE ACKNOWLEDGEMENT
DEVICE LED ACKNOWLEDGEMENT REMARKS
All LEDs blink in BLUE once
per 2 seconds
The device is UNLINKED. IR communication is DISABLED.
The LED of selected channel
blinks in BLUE or GREEN
irregularly.
The device is receiving
commands from the
remote.
BLUE means the device is
unlinked, GREEN means the
device is network linked.
All LEDs are in GREEN and
BLUE alternately.
The device is scanning for
an open network and
linking.
Fast blinking only appears
during network linking.
The LED of selected channel
lit in GREEN for 2 seconds. .
Grouping and network
linking completed.
The LED of selected channel
lit in BLUE for 2 seconds.
Factory default completed.
Exit configuration mode
automatically.
The LED of selected channel
blinks in BLUE or GREEN
twice per second.
The selected channel is in
configuration mode.
Blue means the device is
unlinked, GREEN means
the device is networked.
IR communication ENABLED.
If the LED of other channel lit in
GREEN, it means that channel
has been grouped.
To add an installed OS-NET Button to an existed network,
ensure that the target network is UNLOCKED. Follow the
operation instructions below;
1. Enter into Configuration Mode
2. Assign group(s) to the channel
Conduct EZ-GROUP process and assign group(s) to the
respective channel via the OS-NET Remote Programmer
(SRP-281) as below shown. Refer to the EZ-GROUP
instructions of Programming Guide for more details. The LED
of respective button will blink in BLUE and GREEN alternately
while linking with network. The LED will light in GREEN for 2
seconds to indicate grouping success. To continue assigning
group(s) to other channels, repeat step 1 and 2 on the
respective channel buttons.
Adding the Button to an Existed Network
To change the group(s) already assigned to a channel, ensure
the network is UNLOCKED and operate as instructed below;
Press the LEFT and RIGHT parts of the channel button and hold
for more than 3 seconds to enter the Configuration Mode. The
LED of the button will blink 2 times per second in GREEN.
Input the new group number(s) on the EZ-GROUP setting page
of the remote. Repeat “Assign group(s) to the channel”.
The device will acknowledge setting results with different LED
indications as below.
Changing Group Assignment
Hold the remote
close to the OS-NET
Button as shown to
conduct grouping.
Press the LEFT and RIGHT parts
of the button (ex. channel 1) and
hold for more than 3 seconds to
enter the Configuration Mode. The
LED of respective button will blink
2 times per second in BLUE.
Resume Factory Default
To resume factory default, enter into the Configuration
Mode via any channel button.
Get an OS-NET Remote (SRP-281) and enter to SETTING >
DEVICE > INDIV-SET > DEFAULT.
Select DEVICE and press ENTER to reset the network and
group settings for the device.
NOTE: The device LED will indicate in BLUE after resume
factory default.
1.
2.
3.