Programming Guide
CONTROL SCHEME
The following schemes can be programmed via CONTROL setting of the SRP-281. Depending on the connection of wired Low Voltage Occupancy Sensor (LVOS) and
grouped OS-NET Sensor (ONS)/OS-NET Button (ONB), the ON-PPU may control the load in slightly different patterns.
DEVICE LED ACKNOWLEDGEMENT
The device will acknowledge the setting success or failure with following
indications by device LED in BLUE or GREEN. BLUE means the device is
unlinked and GREEN means the device is network linked.
DEVICE LED ACKNOWLEDGEMENT
LED on Control scheme is set to ON/OFF sensing control
Slow blinking (on-off per 0.5 second) Control scheme is set to vacancy sensing control (VSC)
Blinks twice every 2-second Control scheme is set to plug load control (PLC)
Blinks irregularly in BLUE or GREEN Receiving commands from the remote
Fast blinking in BLUE and GREEN
intermittently
Scanning for an open network and linking
Blinks slow once and fast twice The device is under test mode
Blinks slow once and fast once The device is under burn-in mode
Lit for 2 seconds in GREEN Grouping/setting is completed
WIRING DIAGRAMS
Color Description Function Gauge
White
Black
Red
Red
Neutral
Line
Load
switching
Line
voltage
Relay
contacts
18
AWG
12
AWG
Line Voltage Wires
Color Description Function Gauge
Red
Black
Blue
DC24V
DC-
Sensor
signal input
DC power
supply
Control
24 AWG
Class 2
Low Voltage Wires
Following are basic wiring diagrams for typical controls, consult with an
IR-TEC team member for correct wiring diagram if a more complex control is
required.
A. Occupancy/Vacancy Sensing Control
NOTE: For Vacancy Sensing Control (VSC), at least one OS-NET Button
should be installed and grouped with the ON-PPU-301 to enable
manual-on control.
Black (Line)
White (Neutral)
Red (
Relay)
Red
Black
Green
White
Red (
DC24V)
Black (DC )
Blue (Control)
Red (Relay)
DC+
DC
COM
NO
Occupancy
IR-TEC
Sensor
Load
Line
120/277V
Neutral
Low Voltage
B
S
OS-NET Sensor OS-NET Button
NOTE: If PLC is selected, the OFF-command from OS-NET Button will
be ignored.
Black (Line)
White (Neutral)
Red (
Relay)
Red
Black
Green
White
Red (
DC24V)
Black (DC )
Blue (Control)
Red (Relay)
DC+
DC
COM
NO
Occupancy
IR-TEC
Sensor
Low Voltage
Line
120/277V
Neutral
N
Ground
L
G
B. Plug Load Control
B
S
OS-NET Sensor OS-NET Button
All line voltage wiring connections should be
made inside of junction box.
To obtain optimal wireless communication,
avoid placing the device behind a metal
mesh/plate.
To enable wireless network control, the
ON-PPU-301 must be grouped and linked with
the other OS-NET devices. An “ungrouped”
ON-PPU-301 with low voltage occupancy
sensor connected will only operate in
standalone control.
LVOS ONS ONB ON-PPU-301 Operations
Load ON
Any LVOS detects occupancy
Load OFF --
√
√
√ √
√
√√
√ √
√ √ √
Last active LVOS delay elapses
Delay reset
Not activated
Load ON
Any LVOS/ONS detects occupancy
Load OFF -
Both LVOS and ON-PPU delays elapse
Delay reset
When ONS detects occupancy
Load ON
Any LVOS detects occupancy or ONB is pressed ON
Load OFF -
Last LVOS delay elapses or ONB is pressed OFF
Delay reset
When ONB is pressed ON
Load ON
Any ONS detects occupancy
Load OFF --
ON-PPU delay elapses
Delay reset
When ONS detects occupancy
Load ON
Any ONB is pressed ON
Load OFF --
ON-PPU delay elapses or ONB is pressed OFF
Delay reset
When ONB is pressed ON
Load ON
Any LVOS/ONS detects occupancy or ONB is pressed ON
Load OFF
Both LVOS and ON-PPU delays elapse or ONB is pressed OFF
Delay reset
When ONS detects occupancy or ONB is pressed ON
Load ON
Any ONS detects occupancy or ONB is pressed ON
Load OFF -
ON-PPU delays elapse or ONB is pressed OFF
Delay reset
When ONS detects occupancy or ONB is pressed ON
CONTROL = ON/OFF
The load will be switched ON when ON-PPU receives 1) control signal from a wired
LVOS, or 2) wireless command from a grouped ONS/ONB, and switched OFF when
programmed delay time elapses or receives the OFF-command from a grouped OSB.
If the load was switched OFF via an OSB, the ON-PPU will operate in Presentation
Mode. The load will remain OFF if motion is detected before the delay time elapse.
The ON-PPU will resume to auto-ON, auto-OFF control after delay time elapsed.
“
√
” means “one or more units connected/grouped”
LVOS ONS ONB ON-PPU-301 Operations
Load ON
Load OFF - -
Delay reset
Load ON
Load OFF
Delay reset
Load ON
Load OFF -
Delay reset
Load ON
Load OFF -
Delay reset
CONTROL = VSC
VSC refers to Vacancy Sensing Control. This control requires user to turn ON the load
by pressing a grouped OSB, and the ON-PPU will turn OFF the load when delay time
elapses or receives the OFF-command from a grouped OSB.
Any ONB is pressed ON
ON-PPU delays elapse or ONB is pressed OFF
When ONS detects occupancy or ONB is pressed ON
Any ONB is pressed ON
Both LVOS and ON-PPU delays elapse or ONB is pressed OFF
When ONS detects occupancy or ONB is pressed ON
Any ONB is pressed ON
ON-PPU delay elapses
When ONB is pressed ON
Any ONB is pressed ON
Both LVOS and ON-PPU delays elapse or ONB is pressed OFF
When ONB is pressed ON
√
√
√
√ √
√ √ √
LVOS ONS ONB ON-PPU-301 Operations
Same as ON/OFF control--
Same as ON/OFF Control-
Load ON Any LVOS detects occupancy or ONB is pressed ON
Load OFF - Last LVOS delay elapses
Delay reset When ONB is pressed ON
Same as ON/OFF control--
Load ON Any ONB is pressed ON
Load OFF -- ON-PPU delay elapses
Delay reset When ONB is pressed ON
Load ON Any LVOS/ONS detects occupancy or ONB is pressed ON
Load OFF Both LVOS and ON-PPU delays elapse
Delay reset When ONS detects occupancy or ONB is pressed ON
Load ON
-
Any ONS detects occupancy or ONB is pressed ON
Load OFF ON-PPU delay elapses
Delay reset When ONS detects occupancy or ONB is pressed ON
CONTROL = PLC
PLC refers to Plug Load Control. The ON-PPU will enable the plug load power when it
receives 1) control signal from a wired low voltage occupancy sensor, or 2) wireless
command from a grouped OS-NET Sensor/Button, and switch OFF the plug load
power after the area is vacant and programmed delay time elapsed.
√
√
√
√
√
√
√
√
√
√ √ √
The DELAY timer of ON-PPU will only be activated by receiving the wireless command
from grouped OS-NET devices.
The ON-PPU will transmit OCC signal wirelessly for group control when wired LVOS
detects occupancy.
To prevent unintentionally shutting off the power for plug load control, ensure to set the
DELAY of the ON-PPU longer than the setting of grouped ONS.
Under PLC mode, all OFF-command from the OS-NET Button will be ignored.
1.
NOTE
2.
3.