Product Info
5
3. Technical details
3.1 General
Weight 1,6 kg
Height According to customer application
Wide According to customer application
Depth According to customer application
Housing materials Aluminium, AISI 316
Ingress protection rating IP65…IP68 depending on inlet sealings
Wire Size Maximum 1C 1.0 mm², AWG18, stranded wire
Operating temperature range with battery**) -25…+60 °C
Operating temperature range with external
power supply
-40…+80 °C
Conformity standards
EMC EN 61326-1:2013 ja EN 301489
RF EN 300 220-1 v2.4.1
Vibration EN 60068-2-6
LoRaWAN certified product
**) Note: can vary on battery manufacturer’s technical specification
3.2 Temperature sensor inputs
**) Note: varies with thermocouple type installed
Linear resistance input, Lin. R (S1/S2)
Resistance measurement range 0-3757 Ω
Measurement accuracy ≤ ± 0,1 % of span
Temperature coefficient ≤ ± 0,01 % of span / °C
Pt100/Pt1000 input, RTD (S1/S2)
One or two of the inputs can be set to Pt100/Pt1000 sensors with 2-, 3- or 4-wire connection.
Inputs are short circuit protected and broken wire monitored.
Temperature measurement range**) -200…+800 °C
Measurement accuracy ≤ ± 0,3 °C
Temperature coefficient ≤ ± 0,01 °C / °C
Thermocouple input, TC (S1/S2)
One or two of the inputs can be set to thermocouple sensor inputs. TC-input is broken wire monitored.
Thermocouple types E, J, K, N, R, S, T, B, L and U supported types
Measurement range**) -200 to +1820 °C
Measurement accuracy for types E, J, K, N,
T, U and L
≤ ±1 °C
Measurement accuracy for types B, R and S ≤ ±2 °C
Cold junction compensation (CJC) – 40…+80 °C, accuracy ≤ ± 1 °C