User's Manual

WA020100 - Smart Irrigation Controller
UMAOC001 Rev G
USER MANUAL
7.1.3 UPLINK 03 – CONFIRMATION OF UPLINK PERIOD
After receiving from server the command programming the time slot between uplinks, Watersens will perform
in 3 minutes an uplink to confirm the new setup. The format of the payload is described below
byte 1
byte 2
tf
up
tf. Type of frame (03 - Confirmation uplink time period)
up. Value configured. Possible values:
0 - 3 minutes between uplinks (commissioning purpose)
1..96 - multiple of 15 minutes time slots between uplinks
100 - uplinks only performed when outputs status has changed. Transmission not
forced
Example - confirmation of 3 minutes between uplinks
tf = 03 / up = 00 - Payload: 03 00