28
SBV System Series| Instruction manual v1.2 DEC 2021 |SAF-UM-SBVBus-en-v1.2|© 2021 Inxpect SpA
4. Functioning principles
4.2 Detection fields
4.2.1 Introduction
The field of view of each sensor can be composed of up to four detection fields. Each of the four detection fields
have a dedicated detection signal.
WARNING! Configure the detection fields and associate them with the dual channel safety outputs
according to the risk assessment requirements.
4.2.2 Detection field parameters
These are the programmable parameters for each detection field:
l angular coverage
l detection distance
l safety working mode (Both (default), Always access detection or Always restart prevention) (see
"Safety working modes and safety functions" on page32)
l restart timeout
4.2.3 Angular coverage
The angular coverage has a fixed value in a range from 10° to 100°.
The angular coverage of the detection field must be wider than, or equal to, the angular coverage of the following
detection fields.