CONNECTING FUEL LOCK TO 120V PUMPS
Note: The combined amperage of all fuel pumps connected to both power supplies must not exceed
30 amps.
120v Pump Connection Diagram
1. Shut off power to the device
2. Connect the line side hot conductor (black, from breaker) to the terminal marked “120V” on the right side of the
terminal strip
3. Connect the line side neutral conductor (white, from breaker) to one of the three terminals marked “NEUT”
4. Connect the load side hot conductor (black) for the fuel pump(s) to the terminal marked either “1” or 2” on the
bottom and “120V” on the top.
5. Connect the load side neutral conductor (white) for the fuel pump(s) to one of the remaining terminals marked
“NEUT”
6. Connect the load and line side ground conductors (green or bare) to the ground bar in the bottom left corner of
the Fuel Lockenclosure
Fuel Lock Business
7. Connect the load side hot conductor (black) for the first fuel pump(s) to the terminal marked “1” on the bottom
and “120V” on the top
8. Connect the load side hot conductor (black) for the second fuel pump(s) to the terminal marked “2” on the bot-
tom and “120V” on the top
9. Connect the load side neutral conductor (white) for the second fuel pump(s) to the last remaining terminal
marked “NEUT”