Installation Instructions

Appendix B Terminating Cables
210
Grounding, Continued
Tools and
materials
Tools
Blade, cable cutter, crimping tool for 6 mm
2
and 16 mm
2
grounding cable and hot air gun (refer to Termination of
cables).
Materials
GND-KIT16-OD (16 mm
2
cable)
GND-CAB6-ID (6 mm
2
cable)
Procedure
How to terminate the 16 mm
2
grounding cable to GND-KIT16-OD lugs,
proceed as follows:
Step
Action
1
Cut the grounding cable according to the distance between
equipment and grounding bar.
2
Use the blade to strip 1 cm from each end of the cable, as
below:
3
Perform the following actions:
Slide the M5 grounding lug over the wires at one end of the
cable and crimp it with the special crimping tool.
Cut the heat shrinkable tube in the middle in two equal
pieces in order to use one piece per cable side.
Slide the one piece of the heat shrinkable tube over the
cable. Heat it over rear grounding ring body and down on
to cable jacket using the hot air blower.
4
Repeat step 3 for the other end of the cable in order to
terminate the M8 grounding lug.
End of procedure.
Continued on next page
~
~
1 cm
1 cm