Installation Manual

Table Of Contents
StreetNode™ 6250 PTP
Installation & Cabling Manual - Edition 2.1
77
Appendix C: Terminating Grounding cable, Continued
PonE
How to terminate the grounding cable of StreetNode
TM
6250 PTP, proceed
as follows:
Step
Action
1
Cut the grounding cable according to the distance between PonE and
grounding bar.
2
Use the blade to strip 1 cm from each end of the cable.
3
Perform the following:
a.
Use the tamper-proof torx screwdriver T10 to unscrew the
terminal ring from PonE, as shown below:
b.
Slide the M4 terminal ring over the wires at one end of the cable
and crimp it with the special crimping tool (for 6 mm
2
).
c.
Cut the heat shrinkable tube in the middle in two equal pieces in
order to use one piece per cable side.
d. Slide the one piece of the heat shrinkable tube over the cable.
Heat it over rear grounding ring body and down on to cable
jacket using the hot air blower.
4
Repeat step 3 for the other end of the cable using the appropriate
terminal ring.
M4 ring (PonE side).
Appropriate ring (grounding terminal side)
5
Use the tamper-proof torx screwdriver T10 to screw (applying maximum
tightening torque of 0.9 Nm)
for securing the ring in place.
End of procedure.
~
~
1
cm
1 cm