4.6  EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism 
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections.  
In order to prevent fail status detected by the receivers, which are “listening” the bus, when all 
the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe biasing 
mechanism. This mechanism provides a safe status (a correct voltage level) in the bus when all 
the transmitters’ outputs are in three-state. This mechanism  must be supplied by the Modbus 
Master. 
The  INMBSDAI001R000  device  includes  an  on-board  terminator  resistor  of  120Ω  that  can  be 
connected to the EIA-485 bus by using DIP-switch SW4. 
Some Modbus  RTU  EIA-485 Master devices can  provide also  internal  120Ω terminator  resistor 
and/or  fail-safe  biasing  mechanism  (check  the  technical  documentation  of  the  Master  device 
connected to the EIA-485 network in each case). 